2022-06-28 15:13:11FIRE PROVISO:
  
 1) THERE IS AN INDICATION OF SPRINKLER HEADS AT THE TOP
 OF THE ELEVATOR SHAFT
  
 THESE HEADS MAY NOT BE REQUIRED.
  
 PLEASE REVIEW AND ENSURE COMPLAINCE.
  
 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE
 REQUIRED IN ELEVATOR MACHINE ROOMS, ELEVATOR
 MACHINERY SPACES, CONTROL SPACES, OR HOISTWAYS OF
 TRACTION ELEVATORS INSTALLED IN ACCORDANCE
 WITH THE APPLICABLE PROVISIONS IN NFPA 101, OR THE
 APPLICABLE BUILDING CODE, WHERE ALL OF THE
 FOLLOWING CONDITIONS ARE MET:
 (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL
 ROOM, CONTROL SPACE, OR HOISTWAY OF
 TRACTION ELEVATOR IS DEDICATED TO ELEVATOR EQUIPMENT
 ONLY.
 (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY
 SPACE, CONTROL ROOM, CONTROL
 SPACE, OR HOISTWAY OF TRACTION ELEVATORS ARE PROTECTED
 BY SMOKE DETECTORS, OR OTHER AUTO MATIC FIRE DETECTION,
 INSTALLED IN ACCORDANCE WITH NFPA 72.
 (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL
 SPACE, OR HOISTWAY OF TRACTION ELEVA TORS IS SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY WALLS AND
 FLOOR/CEILING OR ROOF/
 CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF
 NOT LESS THAN THAT SPECIFIED BY THE
 APPLICABLE BUILDING CODE.
 (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE
 PERMITTED TO BE STORED IN ELEVATOR
 MACHINE ROOMS, MACHINERY SPACES, CONTROL ROOMS, CONTROL
 SPACES, OR HOISTWAYS OF TRAC TION ELEVATORS.
 (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC
 TYPE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  