2022-07-06 15:11:04APPROVED WITH PRIVISO:
 THE RECEPTION AREA FOR THE OUTDOOR AIR CALCULATIONS
 SHOULD BE CALCULATED AT 13 PEOPLE, NOT 9, BASED ON FMC
 TABLE 403.3.1.1 FOR A TOTAL OF 89 CFM'S.