| Plan Review Notes For Permit 22061099 |
| Permit Number |
22061099 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-15 12:04:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THANK YOU FOR THE RESPONSE COMMENTS; HOWEVER, I AM | | | AWARE OF THE CALCULATIONS INDICATED. | | | | | | I APOLOGIZE IF I AM MISSING THE INFORMATION NEEDED TO | | | ENSURE THE VERTICAL & HORIZONTAL DUCT LENGHTS | | | (ESPECIALLY TO THE ROOF) WILL NOT HINDER VENTILATION. | | | | | | WHAT IS NOT INDICATED IS THE ACTUAL LENGHTS, HORIZONTAL | | | & VERTICAL AND IN TOTAL, (ESPECIALLY TO THE ROOF) OF | | | THE PROPOSED DUCT WORK AND THE CALULATIONS INDICATING | | | THAT THERE IS SUFFICIENT AIRFLOW TO ENSURE THE GREASE | | | VAPORS ARE EXHAUSTED AND OR THERE IS NO EXXCESSIVE | | | HEAT/SMOKE/VAPORS IN THE KITCHEN. | | | | | | FOR THE OFFICIAL RECORD PLEASE PROVIDE THE CALCULATIONS | | | INDICATING THE DUCT LENGHTS AS PART OF THE | | | CALCULATIONS. | | | | | | | | | 2) THE PAGE 2 OF 5, IF NOT APPLICABLE TO YOUR PROJECT | | | NEEDS TO BE REMOVED FROM THE SUBMITTAL. | | | | | | PLEASE REMOVE THAT PAGE. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|