Plan Review Notes
Plan Review Notes For Permit 22061099
Permit Number 22061099
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-28 15:53:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF AN EXTENDED LENGTH OF
 EXHAUST DUCT VERTICAL & HORIZONTAL.
  
 PER NFPA 96
  
 8.2.1 AIR VELOCITY.
 8.2.1.1* THE AIR VELOCITY THROUGH ANY DUCT SHALL BE NOT
 LESS
 THAN 152.4 M/MIN (500 FT/MIN).
  
 8.2.2 AIR VOLUME.
 8.2.2.1 EXHAUST AIR VOLUMES FOR HOODS SHALL BE OF A
 SUFFICIENT
 LEVEL TO PROVIDE FOR CAPTURE AND REMOVAL OF
 GREASE-LADEN COOK ING VAPORS.
 8.2.2.2* TEST DATA, PERFORMANCE TESTS ACCEPTABLE TO THE
 AUTHOR ITY HAVING JURISDICTION, OR BOTH SHALL BE
 DISPLAYED, PROVIDED ON
 REQUEST, OR BOTH.
  
 PLEASE PROVIDE THE DATA EQUATION DETAILS IN COMPLIANCE.
  
  
 2) THERE IS AN INDICATION OF AN EXTENDED LENGTH OF
 MAKEUP AIR DUCT VERTICAL & HORIZONTAL.
  
 8.3* REPLACEMENT AIR.
 8.3.1 REPLACEMENT AIR QUANTITY SHALL BE ADEQUATE TO
 PREVENT
 NEGATIVE PRESSURES IN THE COMMERCIAL COOKING AREA(S)
 FROM
 EXCEEDING 4.98 PA (0.02 IN. WATER COLUMN).
  
 PLEASE PROVIDE THE DATA EQUATION DETAILS IN COMPLIANCE.
  
  
 3) THERE ARE INDICATIONS OF SUPPRESSION PIPING PAGE
 THAT HAS A SEPARATE ADDRESS WITHIN THE TITLE BLOCK -
 O'BRIENS RESIDENCE - CRAFT MASTER CUSTOM POOLS
  
 PLEASE REVIEW AND CORRECT/REMOVE.
  
  
  
 4) THE SUPPRESSION SYSTEM FOR THIS PROPOSED HOOD SHALL
 BE SUBMITTED UNDER SEPARATE PERMIT & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  