| 2022-09-13 16:05:48 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 22061095 | | | 9/13/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-1: PROVIDE A VENT FOR THE WASHING MACHINE | | | FIXTURE DRAIN- SECS. 909.1, 910.1, & 911.1 FBC P. | | | | | | 2) P-2: PROVIDE A MEANS OF CONTROLLING THERMAL | | | EXPANSION AT THE WATER HEATER- SEC. 607.3 FBC P. | | | | | | 3) P-2: TEMPERED WATER, NOT HOT WATER, SHALL BE | | | DELIVERED FROM THE LAVATORY SINKS. PLEASE INDICATE A | | | MEANS- SEC. 419.5 & 607.1.2. | | | | | | 4) P-2: THE 1/2-INCH HOT WATER SUPPLY PIPES TO THE | | | LAVATORIES ARE EXCEEDING THEIR ALLOWABLE MAXIMUM 2 FT. | | | LENGTHS PER TABLE C404.5.1 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|