2022-07-21 10:50:281ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22061095
 7/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-2 & P-1: PROVIDE PLUMBING FIXTURES
 CALCULATIONS BASED ON THE OCCUPANT LOAD OF THE TENANT
 SPACE AND TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT
 INCLUDES THE REQUIRED AND PROVIDED NUMBER OF FIXTURES.
 PLEASE NOTE THAT SERVICE SINKS AND DRINKING FOUNTAINS
 ARE REQUIRED FIXTURES FOR B OCCUPANCIES.
  
 2) A-2 & P-1: THE SINGLE USER TOILET ROOMS SHALL BE
 LABELED EITHER MALE OR FEMALE BASED ON SEC. 403.2 FBC P
 UNLESS MEETING EXCEPTION 4- OCCUPANT LOAD OF 25 OR
 FEWER.
  
 3) SHEET A-3: SHOW THE GRAB BAR HEIGHTS MEASURED FROM
 THE FINISH FLOORS TO THE TOPS OF THE GRIPPING SURFACES-
 SEC. 609.4 FBC ACC.
  
 4) A-3: SHOW THE HEIGHTS OF THE MIRRORS MEASURED FROM
 THE FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION
 603.3 FBC ACC.
  
 5) A-3: SHOW THE CENTERLINE OF THE TOILET PAPER
 DISPENSER MEASURED FROM THE FRONTS OF THE WATER
 CLOSETS- SECTION AND FIGURE 604.7 FBC ACC.
  
 6) P1- THE SANITARY LAYOUT PLAN IS MISLABELED WATER.
 PLEASE CORRECT AND PROVIDE A WATER PLAN AND RISER
 DRAWING- SEC. 107.3.5.1.3 WPB. THE WATER PLANS SHALL
 SHOW-
  
 A) COLD OR TEMPERED WATER DELIVERY FROM THE LAVATORIES-
 SEC. 419.5 FBC P
  
 B) HOT WATER DELIVERY TO THE CLOTHES WASHER AND MOP
 SINK AND THE MEANS OF LIMITING THE HOT WATER DELIVERY
 TEMPERATURE- SEC. 607.1 & 607.1.1 FBC P.
  
 7) P-1: SHOW THE LOCATION OF THE WATER HEATER AND
 PROVIDE THE FOLLOWING INFORMATION ON THE PLAN.
  
 A) EQUIPMENT SCHEDULE INDICATING MAKE AND MODEL, TANK
 OR TANKLESS, CAPACITY, AND EFFICIENCY RATING- SEC.
 502.1 FBC P AND TABLE C404.1 FBC EC.
  
 B) ACCESS FOR SERVICE, MAINTENANCE AND REPLACEMENT-
 SEC. 501.4.
  
 C) TYPE AND SIZE OF DRAIN PAN AND DRAIN PAN LINE; DRAIN
 PAN LINE RUN AND DISCHARGE LOCATION- SEC. 504.7.
  
 8) P-1: REFER TO SEC. 110.9 WPB AMENDMENTS TO THE FBC-
 IMPACT OF CONSTRUCTION. THE PLAN SHOWS NEW UNDERGROUND
 DRAIN PIPES RUNNING THOUGH THE ADJACENT TENANT SPACE.
 PLEASE PROVIDE DOCUMENTATION THAT INDICATES THE
 PROPERTY OWNER AND TENANT HAVE GRANTED CONSENT FOR THE
 PROPOSED INSTALLATION.
  
 9) SHOW THE LOCATION OF THE REQUIRED TWO CLEANOUT AT
 THE JUNCTION OF THE BUILDING DRAIN AND SEWER LINE-
 SECS- 708.1.3 & 708.1.8 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  