| Date |
Text |
| 2022-07-21 10:50:28 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22061095 |
| | 7/21/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A-2 & P-1: PROVIDE PLUMBING FIXTURES |
| | CALCULATIONS BASED ON THE OCCUPANT LOAD OF THE TENANT |
| | SPACE AND TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT |
| | INCLUDES THE REQUIRED AND PROVIDED NUMBER OF FIXTURES. |
| | PLEASE NOTE THAT SERVICE SINKS AND DRINKING FOUNTAINS |
| | ARE REQUIRED FIXTURES FOR B OCCUPANCIES. |
| | |
| | 2) A-2 & P-1: THE SINGLE USER TOILET ROOMS SHALL BE |
| | LABELED EITHER MALE OR FEMALE BASED ON SEC. 403.2 FBC P |
| | UNLESS MEETING EXCEPTION 4- OCCUPANT LOAD OF 25 OR |
| | FEWER. |
| | |
| | 3) SHEET A-3: SHOW THE GRAB BAR HEIGHTS MEASURED FROM |
| | THE FINISH FLOORS TO THE TOPS OF THE GRIPPING SURFACES- |
| | SEC. 609.4 FBC ACC. |
| | |
| | 4) A-3: SHOW THE HEIGHTS OF THE MIRRORS MEASURED FROM |
| | THE FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION |
| | 603.3 FBC ACC. |
| | |
| | 5) A-3: SHOW THE CENTERLINE OF THE TOILET PAPER |
| | DISPENSER MEASURED FROM THE FRONTS OF THE WATER |
| | CLOSETS- SECTION AND FIGURE 604.7 FBC ACC. |
| | |
| | 6) P1- THE SANITARY LAYOUT PLAN IS MISLABELED WATER. |
| | PLEASE CORRECT AND PROVIDE A WATER PLAN AND RISER |
| | DRAWING- SEC. 107.3.5.1.3 WPB. THE WATER PLANS SHALL |
| | SHOW- |
| | |
| | A) COLD OR TEMPERED WATER DELIVERY FROM THE LAVATORIES- |
| | SEC. 419.5 FBC P |
| | |
| | B) HOT WATER DELIVERY TO THE CLOTHES WASHER AND MOP |
| | SINK AND THE MEANS OF LIMITING THE HOT WATER DELIVERY |
| | TEMPERATURE- SEC. 607.1 & 607.1.1 FBC P. |
| | |
| | 7) P-1: SHOW THE LOCATION OF THE WATER HEATER AND |
| | PROVIDE THE FOLLOWING INFORMATION ON THE PLAN. |
| | |
| | A) EQUIPMENT SCHEDULE INDICATING MAKE AND MODEL, TANK |
| | OR TANKLESS, CAPACITY, AND EFFICIENCY RATING- SEC. |
| | 502.1 FBC P AND TABLE C404.1 FBC EC. |
| | |
| | B) ACCESS FOR SERVICE, MAINTENANCE AND REPLACEMENT- |
| | SEC. 501.4. |
| | |
| | C) TYPE AND SIZE OF DRAIN PAN AND DRAIN PAN LINE; DRAIN |
| | PAN LINE RUN AND DISCHARGE LOCATION- SEC. 504.7. |
| | |
| | 8) P-1: REFER TO SEC. 110.9 WPB AMENDMENTS TO THE FBC- |
| | IMPACT OF CONSTRUCTION. THE PLAN SHOWS NEW UNDERGROUND |
| | DRAIN PIPES RUNNING THOUGH THE ADJACENT TENANT SPACE. |
| | PLEASE PROVIDE DOCUMENTATION THAT INDICATES THE |
| | PROPERTY OWNER AND TENANT HAVE GRANTED CONSENT FOR THE |
| | PROPOSED INSTALLATION. |
| | |
| | 9) SHOW THE LOCATION OF THE REQUIRED TWO CLEANOUT AT |
| | THE JUNCTION OF THE BUILDING DRAIN AND SEWER LINE- |
| | SECS- 708.1.3 & 708.1.8 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |