| Plan Review Notes For Permit 22061095 |
| Permit Number |
22061095 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-19 07:28:43 | REVISE THE MECHANICAL DRAWINGS TO INCLUDE THE BATH | | | EXHAUST FANS AND THE EXHAUST TERMINATION LOCATIONS. | | | SHOW HOW THE 50 CFM EXHAUST FANS WILL MEET FMC TABLE | | | 403.3.1.1 FOOTNOTE E: | | | | | | E. RATES ARE PER WATER CLOSET OR URINAL. THE HIGHER | | | RATE SHALL BE PROVIDED WHERE THE EXHAUST SYSTEM IS | | | DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER RATE | | | SHALL BE | | | PERMITTED ONLY WHERE THE EXHAUST SYSTEM IS DESIGNED TO | | | OPERATE CONTINUOUSLY WHILE OCCUPIED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|