2022-07-19 07:28:43REVISE THE MECHANICAL DRAWINGS TO INCLUDE THE BATH
 EXHAUST FANS AND THE EXHAUST TERMINATION LOCATIONS.
 SHOW HOW THE 50 CFM EXHAUST FANS WILL MEET FMC TABLE
 403.3.1.1 FOOTNOTE E:
  
 E. RATES ARE PER WATER CLOSET OR URINAL. THE HIGHER
 RATE SHALL BE PROVIDED WHERE THE EXHAUST SYSTEM IS
 DESIGNED TO OPERATE INTERMITTENTLY. THE LOWER RATE
 SHALL BE
 PERMITTED ONLY WHERE THE EXHAUST SYSTEM IS DESIGNED TO
 OPERATE CONTINUOUSLY WHILE OCCUPIED.
  