2022-08-01 15:38:20ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL ALL ELECTRIC LOADS IN PANEL SCHEDULE
 AND LOAD CALCULATIONS. IT APPEARS THE AIR CONDITIONING
 AND TANKLESS WATER HEATER LOADS ARE NOT DETAILED. FBC
 107.2 AND NEC 215.5
 2) PLEASE HAVE DESIGNER OF RECORD SEAL AND DIGITALLY
 SIGN PLANS AS REQUIRED. FS471/FS481 DOCUMENTS PREPARED
 BY ARCHITECT/ENGINEER OF RECORD AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE DIGITALLY SEALED AND SIGNED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  