| Plan Review Notes For Permit 22061095 |
| Permit Number |
22061095 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-01 15:38:20 | ELECTRIC REVIEW FAILED | | | 1) PLEASE DETAIL ALL ELECTRIC LOADS IN PANEL SCHEDULE | | | AND LOAD CALCULATIONS. IT APPEARS THE AIR CONDITIONING | | | AND TANKLESS WATER HEATER LOADS ARE NOT DETAILED. FBC | | | 107.2 AND NEC 215.5 | | | 2) PLEASE HAVE DESIGNER OF RECORD SEAL AND DIGITALLY | | | SIGN PLANS AS REQUIRED. FS471/FS481 DOCUMENTS PREPARED | | | BY ARCHITECT/ENGINEER OF RECORD AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|