Plan Review Notes
Plan Review Notes For Permit 22061093
Permit Number 22061093
Review Stop E
Sequence Number 1
Notes
Date Text
2022-07-27 08:19:28ELECTRIC REVIEW FAILED
  
 1) IT APPEARS A RECEPTACLE REQUIRED AS PER NEC 210.52
 (D) IS NOT DETAILED IN MASTER BATHROOM LOCATED WITHIN 3
 FEET OF EACH SINK BASINS. PLEASE CORRECT AS APPLICABLE
 2) PLEASE DETAIL THE REQUIRED SMOKE ALARMS REQUIRED TO
 COMPL WITH FBC RES 314.3
 3) PLEASE DETAIL THAT RELOCATED RECEPTACLES IN MASTER
 BATHROOM WILL COMPLY WITH 20 AMP BRANCH CIRCUIT
 REQUIREMENTS OF NEC 210.11(C)(3)
 4) PLEASE DETAIL NEW WIRING WILL COMPLY WITH ARC FAULT
 CIRCUIT PROTECTION AS REQUIRED BY NEC 210.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  