| 2022-09-26 12:40:28 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. ---NOT ADDRESSED----2020 FPC 1003.3.1 - ONLY DEVICES |
| | DESIGNED TO RECEIVE FATS, OILS AND GREASE SHALL BE |
| | DIRECTED TO THE GREASE WASTE. PLEASE SHOW THAT THE ICE |
| | BINS AND HANDS SINK GO TO THE SANITARY AND NOT THE |
| | GREASE WASTE. |
| | |
| | 2. ---NOT ADDRESSED----2017 WPB AMEND - 107.3 - THE |
| | GREASE INTERCEPTOR REQUIRES A SEPARATE PERMIT AND NEEDS |
| | TO BE APPLIED FOR BEFORE THE RELEASE OF THE MASTER |
| | PERMIT. |
| | |
| | 3. ---NOT ADDRESSED----2020 FPC 905.4 - ON EACH END OF |
| | THE BATHROOMS, THE VENT NEAR THE WATER CLOSET IS |
| | HORIZONTAL AND CANNOT BE UNTIL IT IS 6" ABOVE THE FLOOD |
| | RIM OF THE FIXTURES SERVED. |
| | |
| | 4. ---NOT ADDRESSED----2020 FPC 905.4 - THE VENTS FOR |
| | THE GREASE INTERCEPTORS ARE HORIZONTAL WHILE DRY AND |
| | CANNOT BE. THE VENT CANNOT BE A HORIZONTAL DRY VENT |
| | UNTIL IT IS 6" ABOVE THE FLOOD RIM OF THE FIXTURES |
| | SERVED. |
| | 5. DONE |
| | |
| | 6. ---NOT ADDRESSED----WPB ORD. SEC. 90 - 126 - THE |
| | DISCHARGE FROM AIR HANDLERS/AIR CONDITIONING CONDENSATE |
| | CANNOT DISCHARGE INTO THE SANITARY. IT MUST GO TO THE |
| | STORM OR OTHER APPROVED PLACE OF DISPOSAL. |
| | |
| | 7. ---NOT ADDRESSED----2020 FPC 419.5/607.1.2 - PLEASE |
| | INCLUDE A DETAIL SHOWING COMPLIANCE WITH THE |
| | REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING |
| | STATIONS THAT INCLUDES THE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070. |
| | |
| | |
| | |
| | |
| | ---NOT ADDRESSED----WHEN RESUBMITTING, IT IS HELPFUL TO |
| | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM. |
| | |
| | |