| 2022-09-26 17:17:42 | 2ND REVIEW FMC |
| | PERMIT: 22061092 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-102: IT APPEARS THAT KEF-2 IS EXHAUSTING |
| | TOWARDS THE STAIRWAY DOOR. PLEASE SHOW THIS KEF-2 IS |
| | NOT EXHAUSTING WITHIN 10 FEET OF ANY OPENING INTO THE |
| | BUILDING. ALSO SHOW THE PROPERTY LINE AND THE EXHAUST |
| | DISTANCE TO THE PROPERTY LINE FOR THE KEF???S. FMC |
| | 501.3.1-2 |
| | |
| | 2) PLEASE PROVIDE A LIST OF THE AREAS EF-1 SERVES, IT |
| | APPEARS THAT IT IS EXHAUSTING A DISHWASHER ALONG WITH |
| | THE BATHROOM EXHAUSTS. FBC 107.3.5 |
| | |
| | 3) PLEASE SHOW THAT EF-1 IS MEETING THE REQUIREMENT OF |
| | EXHAUST BEING 3 FEET FROM AN OPENING INTO THE BUILDING. |
| | FMC 501.3.1-3 |
| | |
| | 4) SHEET M-001, WATER SOURCE HEAT PUMP SCHEDULE |
| | INDICATES A TOTAL TONNAGE OF ALL HP???S TO BE 49 TONS. |
| | THE COOLING TOWER SCHEDULE INDICATES CT-1 IS 50 TONS. |
| | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOW A |
| | TOTAL SYSTEM LOADS OF 208105 BTU???S WHICH IF DIVIDED |
| | BY 12,000 WOULD BE 17.34 TONS. PLEASE PROVIDE A |
| | MECHANICAL EQUIPMENT SIZING CALCULATION FOR THE ENTIRE |
| | PROJECT. FBC 107.3.5 |
| | |
| | 5) 2ND ATTEMPT; PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS FOR EACH USE OF SPACE FOR THIS BUILDING. |
| | FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 6) SHEET M-104: PROVIDE A DETAIL DRAWING OF THE KEF???S |
| | PENETRATION OF THE ROOF AND THE ANCHORAGE OF THE |
| | KEF???S. IS THE RETRACTABLE ROOF GOING TO OPEN AROUND |
| | THESE KEF???S? FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |