| 2022-10-07 08:57:28 | ADDITION AND REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS |
| | AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.3.4 |
| | |
| | 2) PLEASE SHOW ON THE DRAWINGS THAT TERMITE TREATMENT |
| | IS A REQUIREMENT PER FBC 1816 |
| | |
| | 3) PLEASE SHOW WALL DESIGNATIONS ON THE FLOOR PLANS - |
| | SHOW FIRE WALLS ETC. FBC WPB 107.2 |
| | |
| | 4) BASED ON THE DISTANCE FROM THE CENTER OF THE ALLY |
| | (SHOW THE DISTANCE) TO THE REAR WALL. THE REAR WALL |
| | NEEDS TO SHOW AS 1 HOUR FIRE RATED - FBC TABLE 602 |
| | |
| | 5) BASED ON THE DISTANCE FROM THE CENTER OF THE ALLY |
| | (SHOW THE DISTANCE) TO THE REAR WALL - PLEASE SHOW THE |
| | ALLOWABLE NON PROTECTED OR PROTECTED OPENING |
| | CALCULATIONS FOR EACH FLOOR - FBC TABLE 705.8 |
| | |
| | 6) PLEASE SHOW THE POOL BARRIER (DOORS, LOCKS, LATCH |
| | HEIGHT ETC.) AT THE STAIR AND ELEVATOR DOORS TO COMPLY |
| | WITH FBC 454.1.3.1.9 |
| | |
| | 7) PLEASE SHOW THE ACCESSIBLE POOL ENTRY - FBC A 242.2 |
| | SWIMMING POOLS. |
| | AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE |
| | PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY |
| | SHALL BE SWIMMING POOL LIFTS COMPLYING WITH 1009.2; |
| | SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS |
| | COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH |
| | 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST |
| | ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY |
| | WITH 1009.2 OR 1009.3. |
| | |
| | 8) FOR THE REMODELED GROUND FLOOR = PLEASE SHOW THE |
| | DIFFERENT DINING AREA LOCATIONS FOR THE ACCESSIBLE |
| | SEATING - FBC 226 |
| | |
| | 9) FOR THE REMODELED GROUND FLOOR = PLEASE SHOW AT |
| | LEAST 1 ACCESSIBLE SEAT AT EACH BAR LOCATION (SHOW |
| | COUNTER HEIGHT, KNEE AND TOE CLEARANCES ETC. ) - FBC |
| | 226.2 |
| | |
| | 10) PLEASE PROVIDE TYPICAL GUARDRAIL AND HANDRAIL |
| | DETAILS - SHOWING HEIGHTS, OPENING SPECS., HANDRAIL |
| | EXTENSIONS ETC. FBC 1014 AND 1015 |
| | |
| | 11) PLEASE PROVIDE A THRESHOLD INSPECTION PLAN - FBC |
| | (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION PLAN. THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| | THE ENGINEER OF RECORD. |
| | |
| | 12) THE STRUCTURAL DRAWINGS NEED TO CONTAIN THIS NOTE - |
| | THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | 13) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER |
| | THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". |
| | YOU CAN E MAIL ME AND ASK FOR A COPY. |
| | |
| | 14) PLEASE PROVIDE A COPY OF THE UNITY OF TITLE. |
| | |
| | 15) A SEPARATE PERMIT IS REQUIRED FOR THE BUILDING |
| | DEMO. |
| | |
| | 16) ITEMS SUCH AS BUT NOT LIMITED TO RAILING, EXTERIOR |
| | WINDOW, DOOR AND ROOFING SYSTEMS PRODUCT APPROVALS MAY |
| | BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED |
| | ON THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED |
| | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL |
| | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL |
| | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 17) STRUCTURAL AND FIRE PROTECTION DRAWINGS DO NOT SHOW |
| | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| | DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |