| 2022-06-29 13:44:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET E 000 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| | DEVICES, EQUIPMENT, NOR FIRE AMARM WORK |
| | |
| | THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT |
| | DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE |
| | DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 2) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF ANY |
| | ELECTRICAL SHEETS SHOWING THE LOCATION OF REQUIRED EXIT |
| | LIGHTS & EMERGENCY LIGHTING. |
| | |
| | EXIT MARKINGS, EXIT TAVEL PATH SIGNS AND EMEREGENCY |
| | LIGHTING ARE REQUIRED BY NFPA 101 CH 12 NEW ASSEMBLY |
| | OCCUPANCY & CH 7 MEANS OF EGRESS. |
| | |
| | PLEASE PROVIDE SPECIF DETAILS IN COMPLIANCE WITH THE |
| | CODE. |
| | |
| | |
| | 3) SHEET A 203 - THERE IS AN INDICATION OF POOL |
| | EQUIPMENT ROOM/AREA/PLATFORM |
| | |
| | THE DOOR LEADING TO THIS AREA SHALL BE PLACARD PER NFPA |
| | 1 & 704 FOR THE CHEMICAL STORAGE. |
| | |
| | |
| | 3A) SHEET A 203 - PLEASE PROVIDE THE TYPE AND AMOUNT OF |
| | PROPOSED CHEMICAL STORAGE IN THE POOL EQUIPMENT AREA. |
| | |
| | PER NFPA 1 |
| | |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |