| Date |
Text |
| 2022-07-30 18:52:32 | |
| | |
| | 1) 225 KVA TRANSFORMER TO BE INSTALLED PER 450.21(B) |
| | |
| | OVER 112 KVA. INDIVIDUAL DRY-TYPE TRANSFORMERS OF MORE |
| | THAN 112KVA RATING SHALL BE INSTALLED IN A TRANSFORMER |
| | ROOM |
| | OF FIRE-RESISTANT CONSTRUCTION. UNLESS SPECIFIED |
| | OTHERWISE IN THIS ARTICLE, THE TERM FIRE RESISTANT |
| | MEANS A CONSTRUCTION HAVING A |
| | MINIMUM FIRE RATING OF 1 HOUR. |
| | |
| | 2) PLEASE LAYOUT ELECTRICAL ROOM IN NEW BAR AREA FOR |
| | WORKING CLEARANCES AND OVERHEAD CLEARANCES FOR |
| | MECHANICAL EQUIPMENT. 110.26 |
| | |
| | 3) ALL OUTDOOR OUTLETS 125, AND 240 VOLT TO BE GFCI |
| | PROTECTED PER 210.8(B) 50 AMPERES SINGLE PHASE AND 100 |
| | AMPERES FOR THREE PHASE. |
| | |
| | 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 |
| | AMPERES OR LESS AND THREEPHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100 |
| | AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS |
| | SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | |
| | RECEPTACLES OF 15 AND 20 AMPERES IN A WET LOCATION. |
| | RECEPTACLES OF 15 AND 20 AMPERES, 125 AND 250 VOLTS |
| | INSTALLED |
| | IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS |
| | WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS |
| | INSERTED. AN OUTLET |
| | BOX HOOD INSTALLED FOR THIS PURPOSE SHALL BE LISTED AND |
| | SHALL BE IDENTIFIED AS ?EXTRA-DUTY.? OTHER LISTED |
| | PRODUCTS, ENCLOSURES, OR |
| | ASSEMBLIES PROVIDING WEATHERPROOF PROTECTION THAT DO |
| | NOT UTILIZE AN OUTLET BOX HOOD NEED NOT BE MARKED |
| | ?EXTRA DUTY.? |
| | |
| | 4) RECEPACLES THAT LOOK LIKE THEY ARE FLOOR BOXES IN |
| | THE POOL AREA DECK AND OTHER AREAS ON ROOF DECK PLEASE |
| | SHOW DETAIL. 406.9 |
| | |
| | 5) COVERS FOR RECEPATCLES INSTALLED IN DAMP/WET |
| | LOCATION SHALL MEET THE REQUIREMENTS OF 406.9(A) |
| | |
| | 406.9(A) DAMP LOCATIONS. A RECEPTACLE INSTALLED |
| | OUTDOORS IN A LOCATION PROTECTED FROM THE WEATHER OR IN |
| | OTHER DAMP LOCATIONS |
| | SHALL HAVE AN ENCLOSURE FOR THE RECEPTACLE THAT IS |
| | WEATHERPROOF WHEN THE RECEPTACLE IS COVERED (ATTACHMENT |
| | PLUG CAP NOT |
| | INSERTED AND RECEPTACLE COVERS CLOSED). |
| | |
| | 6) SOME OF THE SPEAKERS ARE ON 120 VOLT CIRCUITS AND |
| | SOME ARE NOT, PLEASE DISGUIGUISH BETWEEN THE TYPES |
| | 110.3 |
| | |
| | 7) FANS INSTALLED AROUND POOL NEED TO SHOW DISTANCE AND |
| | HEIGHT FROM POOL. 680.22(B)(1) |
| | |
| | 8) MDP1LOAD CALCULATION SHOWS EXISTING? I DO NOT SEE |
| | PANELS A,B AND OTHER LOADS NOT LISTED ON PANEL SCHEDULE |
| | FOR MDP1. 220 |
| | PLEASE SHOW HOW THE LOAD CALCULATION WAS ARRIVED AT FOR |
| | MDP1, AND MDP2 YOU CAN NOT USE A DEMAND ON A PANEL THAT |
| | WAS |
| | ALREADY DEMANDED WHEN SIZING THE PANEL. |
| | |
| | 9) IS THE VIP LEVEL AND THE ROOF LEVEL THE SAME? |
| | |
| | 10) NEED A LAYOUT OF THE POOL EQUIPMENT ON PLAN. |
| | |
| | |