Plan Review Notes
Plan Review Notes For Permit 22061090
Permit Number 22061090
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-15 11:22:14PROVIDE THE ENERGY CALCULATIONS FOR THE GARAGE. FEC
 101.5.1.1.2
  
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THE MINI SPLIT IN THE GARAGE. FEC R403.7.1
  
 REMOVE THE RETURN AIR DUCT FROM THE ROOM ATTACHED TO
 THE NEW OFFICE, IF IT IS TO BE A CLOSET. IT IS NOT
 IDENTIFIED IN THE RENOVATION. FRC M1602.3
  