| 2022-07-13 13:30:30 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22061077 |
| | 7/13/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) TWO DWELLINGS ON THE SAME LOT WILL REQUIRE WATER |
| | USERS TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE |
| | POINT OF DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW |
| | DEVICE WILL BE REQUIRED FOR THE WATER METER PER SECS. |
| | C, D, & E WEST PALM BEACH UTILITIES CROSS-CONNECTION |
| | MANUAL. PLEASE ADD THE MAKE AND MODEL OF THE DEVICE TO |
| | THE BACKFLOW PREVENTION DEVICE SCHEDULE ON SHEET P801, |
| | AND SUBMIT THE CIVIL PLANS REFERENCED IN THE SCHEDULE. |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 2) E-1: CORRECT THE RISER TO SHOW A 2-INCH TRAP FOR THE |
| | STANDPIPE- TABLE P3101.7 FBC RES. |
| | 3) SHEET E-1: SHOW THE LOCATION OF THE NEW WATER |
| | HEATER- SEC. P2801.1 FBC RES. AND PROVIDE AN EQUIPMENT |
| | SCHEDULE- SEC. P2801.4 FBC RES. THE EQUIPMENT SCHEDULE |
| | SHALL INDICATE THE MAKE AND MODEL, TYPE- TANK OR |
| | TANKLESS, GALLON SIZE, EFFICIENCY RATING, AND |
| | ELECTRICAL CIRCUITRY. A) PAN AND PAN DRAIN DETAILS ARE |
| | REQUIRED FOR STORAGE TANK INSTALLATIONS- SEC. P2801.6 |
| | FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |