Plan Review Notes
Plan Review Notes For Permit 22061065
Permit Number 22061065
Review Stop M
Sequence Number 2
Notes
Date Text
2022-11-07 06:29:332ND REVIEW FMC
 PERMIT: 22061065
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: IF KEYNOTE 1 DOES NOT APPLY THEN PLEASE
 REMOVE KEYNOTE 1. FBC 17.3.5
  
 2) PLEASE SHOW THE RETURN AIR PATH FROM THE MAIN ENTRY.
 FMC 601.6
  
 3) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE
 NOT SUBMITTED IN THIS RESUBMITTAL. PLEASE SUBMIT A
 MECHANICAL EQUIPMENT SIZING CALCULATIONS ACCORDING TO
 FEC C403.2.1
  
 4) THE MECHANICAL SYSTEM THAT IS CONDITIONING THE
 PUBLIC AREA OF THIS NEW CARWASH WILL NEED TO COMPLY
 WITH THE HVAC EQUIPMENT PERFORMANCE REQUIREMENTS OF FEC
 C403.2.3
  
 5) PLEASE PROVIDE A REVISED SHEET M2 INDICATING THAT
 THE CONDENSING UNIT ON THE ROOF WILL NOW MEET THE 10???
 GUARD PROTECTION REQUIREMENT OF FMC 304.11
  
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND
 AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN
 ACCORDANCE
 WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N OR
 BY AN APPROVED EQUIVALENT COMPUTATIONAL PROCEDURE
 USING THE DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 HEATING AND COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT
 FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE ENERGY
 RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN
 ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT
 HANDBOOK BY AN APPROVED EQUIVALENT COMPUTATIONAL
 PROCEDURE. DESIGN LOADS SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE MECHANICAL PERMIT.
  
 EXCEPTION:
 WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A REGISTERED
 ENGINEER, THE ENGINEER HAS THE OPTION OF
 SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE
 BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING
 CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE
 FOLLOWING
 (BY ZONE):
 1. PROJECT NAME/OWNER
 2. PROJECT ADDRESS
 3. AREA IN SQUARE FEET
 4. SIZING METHOD USED
 5. OUTDOOR DRY BULB USE
 6. INDOOR DRY BULB
 7. OUTDOOR WET BULB USED
 8. GRAINS WATER (DIFFERENCE)
 9. TOTAL SENSIBLE GAIN
 10.TOTAL LATENT GAIN
 11.RELATIVE HUMIDITY
 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR
 13.TOTAL HEATING REQUIRED WITH OUTSIDE AIR
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  