| 2022-11-07 06:29:33 | 2ND REVIEW FMC |
| | PERMIT: 22061065 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: IF KEYNOTE 1 DOES NOT APPLY THEN PLEASE |
| | REMOVE KEYNOTE 1. FBC 17.3.5 |
| | |
| | 2) PLEASE SHOW THE RETURN AIR PATH FROM THE MAIN ENTRY. |
| | FMC 601.6 |
| | |
| | 3) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE |
| | NOT SUBMITTED IN THIS RESUBMITTAL. PLEASE SUBMIT A |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS ACCORDING TO |
| | FEC C403.2.1 |
| | |
| | 4) THE MECHANICAL SYSTEM THAT IS CONDITIONING THE |
| | PUBLIC AREA OF THIS NEW CARWASH WILL NEED TO COMPLY |
| | WITH THE HVAC EQUIPMENT PERFORMANCE REQUIREMENTS OF FEC |
| | C403.2.3 |
| | |
| | 5) PLEASE PROVIDE A REVISED SHEET M2 INDICATING THAT |
| | THE CONDENSING UNIT ON THE ROOF WILL NOW MEET THE 10??? |
| | GUARD PROTECTION REQUIREMENT OF FMC 304.11 |
| | |
| | C403.2.1 CALCULATION OF HEATING AND COOLING LOADS. |
| | DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND |
| | AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN |
| | ACCORDANCE |
| | WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N OR |
| | BY AN APPROVED EQUIVALENT COMPUTATIONAL PROCEDURE |
| | USING THE DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| | HEATING AND COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT |
| | FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE ENERGY |
| | RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN |
| | ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT |
| | HANDBOOK BY AN APPROVED EQUIVALENT COMPUTATIONAL |
| | PROCEDURE. DESIGN LOADS SHALL BE ATTACHED TO THE CODE |
| | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| | SIZING CALCULATION SHALL BE SUBMITTED WITH |
| | THE APPLICATION FOR THE MECHANICAL PERMIT. |
| | |
| | EXCEPTION: |
| | WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A REGISTERED |
| | ENGINEER, THE ENGINEER HAS THE OPTION OF |
| | SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE |
| | BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING |
| | CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE |
| | FOLLOWING |
| | (BY ZONE): |
| | 1. PROJECT NAME/OWNER |
| | 2. PROJECT ADDRESS |
| | 3. AREA IN SQUARE FEET |
| | 4. SIZING METHOD USED |
| | 5. OUTDOOR DRY BULB USE |
| | 6. INDOOR DRY BULB |
| | 7. OUTDOOR WET BULB USED |
| | 8. GRAINS WATER (DIFFERENCE) |
| | 9. TOTAL SENSIBLE GAIN |
| | 10.TOTAL LATENT GAIN |
| | 11.RELATIVE HUMIDITY |
| | 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR |
| | 13.TOTAL HEATING REQUIRED WITH OUTSIDE AIR |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |