| 2022-07-19 11:32:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22061065 879 W EXECUTIVE CENTER DR |
| | |
| | 1ST REVIEW |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| | |
| | 2. PLAN SHEET A1B/ WATER CLOSET REAR WALL VIEW DETAIL: |
| | TO SHOW COMPLIANCE WITH FBC ACC604.5.2, REMOVE 6 INCH |
| | MEASUREMENT FROM SIDE WALL TO GRAB BAR AS IT CONFLICTS |
| | WITH 17 INCH MEASUREMENT FROM SIDEWALL TO CENTERLINE OF |
| | THE WATER CLOSET |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM |
| | AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| | OTHER SIDE PER FBC ACC 604.5.2 |
| | |
| | 3. PLAN SHEET A1B/ WALL HUNG SINK WITH MIRROR DETAIL: |
| | PER FBC ACC 603.3, MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT THE MAXIMUM |
| | 40 INCH DIMENSION IS TO THE REFLECTING SURFACE OF THE |
| | MIRROR AS THE FRAME IS NOT DIMENSIONED.. |
| | |
| | 4. PER WPB FBC 107.2.1 AND 107.3.4, MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE FOLLOWING |
| | SHALL BE PROVIDED FOR THE FOLLOWING: |
| | ***A) WATER HEATER |
| | ***B) BACKFLOW PREVENTER DEVICES |
| | ***C) THERMOSTATIC MIXING VALVES |
| | ***D) MOP SINK FAUCET |
| | ***E) ACO TRENCH DRAIN |
| | ***F) OIL/WATER SEPARATOR |
| | ***G) RECLAIM TANKS |
| | ***H) HEAVY DUTY TRAFFIC LIDS FOR THE INTERCEPTOR AND |
| | RECLAIM TANKS |
| | ***I) WASH EQUIPMENT LISTED IN PINK BIRD 2 CAR WASH |
| | EXPRESS INSTALLATION 2-24-22-02 |
| | ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE PER WPB FBC |
| | 107.2.1 AND 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| | ACCORDANCE WITH WPB FBC 107.3.4.1. DEFERRED SUBMITTALS |
| | SHALL BE LISTED ON THE PLANS. |
| | |
| | 5. OIL/WATER SEPARATOR: A SEPARATE PERMIT IS REQUIRED |
| | HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN PERMIT IS |
| | ALSO REQUIRED. PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING: |
| | ***A) PROVIDE AN ENLARGED PIPING DIAGRAM SHOWING THE |
| | LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED BY THE |
| | MANUFACTURER AND FBC PL 1003.9. |
| | ***B) PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR |
| | ON THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | (INCLUDING STRUCTURAL) THAT INDICATE THE LISTING AND |
| | LABELING OF THE UNIT- FBC PL 1003.4.2 |
| | ***C) PROVIDE SIZING CALCULATIONS PER THE MANUFACTURER |
| | IN ACCORDANCE WITH FBC PL 1003.4.2.2- NOT LESS THAN 6 |
| | CU. FT. FOR THE FIRST 100 SQ. FT. OF AREA TO BE DRAINED |
| | PLUS 1 CU. FT. FOR EACH ADDITIONAL 100 SQ. FT. |
| | ***D) PROVIDE A SITE SPECIFIC, DIMENSIONED INSTALLATION |
| | DIAGRAM (PLAN AND RISER) SHOWING THE BURIAL DEPTH AND |
| | INLET AND OUTLET LOCATIONS, CLEAN OUT AND SAMPLING PORT |
| | LOCATIONS AND SIZES. PLEASE NOTE A SAMPLING PORT |
| | CONSISTING OF A 4-INCH TWO-WAY CLEANOUT TO BE USED AS A |
| | SAMPLING PORT MAY BE REQUIRED. PLEASE CONTACT THE CITY |
| | OF WEST PALM BEACH UTILITIES DEPT. FOR ADDITIONAL |
| | REQUIRED INSPECTION AND TEST SAMPLING INFORMATION AND |
| | GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065 |
| | OR 561-822-2274 OR EMAIL [email protected]. |
| | ***E) HEAVY DUTY TRAFFIC LIDS ARE REQUIRED FOR TANK |
| | ACCESS OPENINGS- FBC PL 305.7 & 1003.10. PLEASE SUBMIT |
| | SPECS FOR THE LIDS. F) ALL SUBMITTALS SHALL BE APPROVED |
| | AND STAMP BY THE DESIGN PROFESSIONAL IN RESPONSIBLE |
| | CHARGE- SECTION 107.2.1, 107.3.4. WPB. SUBMITTALS MAY |
| | BE DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. |
| | |
| | 6. RECLAIMED WATER SYSTEM- PER WPB FBC 107.2.1 WPB AND |
| | FBC PL 1301.1 & 1304.3 FBC PL, PROVIDE THE FOLLOWING: |
| | ***A) PROVIDE A COMPLETE PIPING DIAGRAM (PLAN AND |
| | RISER) THAT SHOWS THE PIPE RUNS FROM THE TANKS TO THE |
| | EQUIPMENT ROOM AND TO THE CONVEYOR. INCLUDE THE |
| | LOCATIONS OF TANK CLEANOUTS, VENTS AND OTHER |
| | APPURTENANCES WHERE REQUIRED BY MANUFACTURER'S |
| | SPECIFICATIONS. |
| | ***B) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE |
| | TANKS, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKS (INCLUDING STRUCTURAL), THE RECLAIM UNIT, AND THE |
| | PIPING- FBC PL 1301.9.2, 1304.3 AND 1304.1.3. |
| | ***C) INDICATE HOW THE TANKS WERE SIZED AND PROVIDE |
| | CALCULATIONS. |
| | ***D) PROVIDE SITE SPECIFIC, DIMENSIONED TANK AND TANK |
| | INSTALLATION DIAGRAMS SHOWING ALL COMPONENTS IF THE |
| | TANKS AND BURIAL DEPTHS, WATER INLET AND OUTLET |
| | LOCATIONS ETC.- FBC PL 1309.3, 1309.7. |
| | ***E) HEAVY DUTY TRAFFIC LIDS ARE REQUIRED FOR TANK |
| | ACCESS OPENINGS- FBC PL 305.7 & 1309.6. PLEASE SUBMIT |
| | SPECS FOR THE LIDS. |
| | ***F) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| | 107.2.1 & 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| | ACCORDANCE WITH WPB FBC 107.3.4.1. |
| | |
| | 7. CAR WASH SYSTEM: PER WPB FBC 107.2.1 AND 107.3.4, |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| | MANUALS FOR ALL WASH EQUIPMENT LISTED IN PINK BIRD 2 |
| | CAR WASH EXPRESS INSTALLATION 2-24-22-02 FOR THE |
| | EQUIPMENT ROOM AND TUNNEL. PLEASE SUBMIT SHOP DRAWINGS |
| | FOR THE TUNNEL EQUIPMENT INSTALLATIONS. SUBMITTALS MAY |
| | BE DEFERRED IN ACCORDANCE WITH WPB FBC 107.3.4.1. |
| | ***A) PER SECTION 107.2.1 & 107.3.5.1.3 WPB PROVIDE A |
| | COMPLETE WATER PIPING DIAGRAM OR RISER DRAWING FOR THE |
| | EQUIPMENT ROOM AND WASH TUNNEL. SHOW LOCATIONS OF |
| | POTABLE WATER CONNECTIONS, BACKFLOW PREVENTERS, VALVES, |
| | AND SHUTOFFS FOR WASH EQUIPMENT. |
| | |
| | 8. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | AND SHALL COMPLY WITH THE REQUIREMENTS OF FBC PL 605.3, |
| | TABLE 605.3, 605.4, TABLE 605.4, 605.5, TABLE 605.5, |
| | 605.7 AND TABLE 605.7. PER WPB FBC 107.2.1, PROVIDE |
| | NOTE ON PLANS STATING THE SAME. |
| | |
| | 9. P5/RPZ AT THE DOMESTIC WATER ENTRY: ALTHOUGH THE |
| | MANUFACTURER'S SPECIFICATIONS/INSTALLATION MANUALS DO |
| | NOT CLEARLY STATE IT, THE LF-009 RPZ IS MEANT TO BE |
| | INSTALLED ONLY IN THE HORIZONTAL POSITION. THIS IS |
| | REINFORCED BY THE FACT THAT THE MANUFACTURER?S |
| | SPECIFICATIONS/INSTALLATION MANUALS FOR THE LF-009 RPZ |
| | NOTES THAT THE UNIT MAY BE INSTALLED IN EITHER A |
| | VERTICAL OR HORIZONTAL POSITION DUE TO THE LOCATION OF |
| | THE RELIEF VALVE IN RELATION TO THE NUMBER 1 CHECK |
| | VALVE. PER WPB FBC 107.2.1, REVISE P5/DOMESTIC WATER |
| | ENTRY TO SHOW THE SPECIFIED LF-009 RPZ IN A HORIZONTAL |
| | POSITION; INCLUDE THE RELIEF VALVE DISCHARGE WITH AIR |
| | GAP AND SUPPORT DETAILS. IN LIEU OF THE HORIZONTAL |
| | POSITION, SPECIFY A PRV SUITED FOR VERTICAL |
| | INSTALLATION AND PROVIDE DETAIL; INCLUDE THE RELIEF |
| | VALVE DISCHARGE WITH AIR GAP AND SUPPORT DETAILS. IT |
| | SHOULD BE NOTED THAT CIVIL DRAWING C5 PROVIDES A RPPA |
| | BACKFLOW PREVENTION DEVICE IN THE WATER SERVICE AT THE |
| | METER LOCATION TO THE BUILDING. |
| | |
| | 10. THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER |
| | PIPING, FROM THE SOURCE OF HOT WATER TO THE FIXTURES |
| | THAT REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 |
| | FEET (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER PER FBC PL 607.2. |
| | IT APPEARS THE HOT WATER PIPING FROM THE WATER HEATER |
| | TO THE LAVATORY EXCEEDS 50 FEET. PER WPB FBC 107.2.1, |
| | SHOW COMPLIANCE WITH FBC PL 607.2. |
| | REFER TO TABLE C404.5.1 FBC EC- THE 1/2 -INCH HOT WATER |
| | PIPE TO THE LAVATORY SHALL NOT EXCEED 2 FEET FROM THE |
| | HOT WATER SOURCE. |
| | ***A) IF RECIRCULATED OR HEAT TRACE SYSTEM IS APPLIED, |
| | A DETAIL AND SPECIFICATION IS REQUIRED FOR THE |
| | RECIRCULATING PUMP SHOWING PIPING, VALVES AND |
| | APPURTENANCES AS WELL AS INTEGRATION WITH THE WATER |
| | HEATER PIPING OR THE HEAT TRACE SYSTEM, WHICHEVER IS |
| | APPLICABLE. |
| | |
| | 11. P4/GENERAL NOTE 3: PER FBC PL 605.2.1, NOTE SHALL |
| | STATE "LEAD FREE SOLDERED JOINTS", NOT "95/5 SOLDERED |
| | JOINTS". |
| | |
| | 12. P2: THERE ARE NUMBERED WINDOW SYMBOLS ON THE PLAN |
| | THAT SHOULD BE SUPPORTED WITH KEY NOTES, BUT THERE ARE |
| | NO CORRESPONDING KEY NOTES. PER WPB FBC 107.2.1, PLEASE |
| | CLARIFY. |
| | |
| | 13. P2: PER WPB FBC 107.2.1, CLARIFY THE PURPOSE OF THE |
| | 1-1/2 INCH VALVED AND CAPPED COLD WATER LINE LINE |
| | (WINDOW SYMBOL 4). PLEASE NOTE THAT PER FBC PL 608.1 |
| | AND 1301.9.4, A BACKFLOW PREVENTER IS REQUIRED AT THE |
| | CONNECTION POINT FOR THE WASH EQUIPMENT. PROVIDE A |
| | BACKFLOW PREVENTER ASSEMBLY AT THIS LOCATION AND |
| | INDICATE THE TYPE PER FBC PL 608.3. THE EQUIPMENT |
| | SYSTEM SHALL BE COMPLETELY ISOLATED FROM THE POTABLE |
| | WATER SYSTEM. PLEASE SEE COMMENT 6. |
| | |
| | 14. P4/SANITARY RISER; PER WPB CODE OF ORDINANCE |
| | CHAPTER 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE |
| | (INTERPRET THIS AS ANY CONDENSATION FROM EVAPORATOR |
| | COILS) SHALL NOT DISCHARGE TO THE CITY UTILITIES |
| | SANITARY SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM |
| | THE UTILITIES DEPARTMENT. YOU MAY CONTACT MR. RICK |
| | ROSSANO IN ENGINEERING AT 561-494-1098 FOR ADDITIONAL |
| | INFORMATION. MOVING FORWARD, REMOVE THE DRAIN FOR THE |
| | A/C CONDENSATE FROM THE SANITARY AND DISCHARGE THE |
| | CONDENSATE TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1, |
| | PROVIDE ROUTING AND DRYWELL DETAIL. |
| | |
| | 15.PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY |
| | WITH FBC EC TABLE C404.2 |
| | |
| | 16. SEE P4/GENERAL NOTE 3: INSULATION SPECIFICATION FOR |
| | HOT WATER INSULATION SHALL COMPLY WITH FBC EC C404.4 |
| | (A-E) AND TABLE C403.2.10. PER WPB FBC 107.2.1 |
| | THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN |
| | IN TABLE C403.2.10:A.RECIRCULATING SYSTEM PIPING, |
| | INCLUDING THE SUPPLY AND RETURN PIPING OF A CIRCULATING |
| | TANK TYPE WATER HEATER. |
| | ***A) THE FIRST 8 FEET OF OUTLET PIPING FOR A |
| | CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM. |
| | ***B) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO |
| | RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING. |
| | ***C) THE INLET PIPING BETWEEN THE STORAGE TANK AND A |
| | HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM. |
| | ***D) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT |
| | TRACE OR IMPEDANCE HEATING). |
| | |
| | 17. PER WPB FBC 107.2.1, PROVIDE DETAIL AND |
| | SPECIFICATION FOR SUPPORT BRACKET AND ANCHORS FOR WALL |
| | MOUNTED WATER HEATER. |
| | |
| | 18. P2/ROOF DRAINAGE: NOTE IN ROOF DRAIN CALCULATIONS |
| | (SEE P2/ROOF DRAINAGE) STATES DISCHARGES TO SITE STORM |
| | SEWER; P1 INDICATES TWO (2) STORM BUILDING DRAINS WITH |
| | NOTE "CONNECT TO CIVIL". CIVIL (SEE C4) DOES NOT |
| | INDICATE STORM BUILDING SEWER, ONLY PAVEMENT DRAINAGE |
| | WITH EXFILTRATION TRENCH AND NO PROVISION FOR BUILDING |
| | STORM DISCHARGE. PER WPB FBC 107.2.1, PROVIDE CLEAR |
| | PLANS WITH CLEAR INSTRUCTION FOR TERMINATION OF |
| | BUILDING STORM DISCHARGE |
| | |
| | 19. A3 ROOF PLAN/OVERFLOW SCUPPER DETAIL: THE SCUPPER |
| | DETAIL DOES NOT APPEAR IN COMPLIANCE WITH SECTION |
| | 1503.4.2.1 FBC B WHICH INDICATES THE SCUPPERS SHALL BE |
| | PLACED IN THE PARAPET WALLS NOT LESS THAN 2 INCHES NOR |
| | MORE THAN 4 INCHES ABOVE THE ROOF COVERING. PER WPB FBC |
| | 107.2.1, REVISE NOTE TO REFLECT THE REQUIREMENT. |
| | |
| | 20. PER WPB FBC 107.2.1, PROVIDE STORM RISER DIAGRAM. |
| | |
| | 21. P1/SANITARY DRAINAGE AND SIZING CHART: TRENCH DRAIN |
| | IS NOTED WITH 4 INCH TRAP WITH A DFU VALUE OF 2; PER |
| | FBC PL TABLE 709.1, FOOTNOTE A), THE VALUE FOR A 4 INCH |
| | TRAP SHALL BE 6. |
| | |
| | 22. P4/WATER HEATER SCHEDULE AND DETAIL: |
| | ***A) DETAIL SHOWS RELIEF LINE DISCHARGING TO A FLOOR |
| | DRAIN. NO FLOOR DRAIN IS SHOWN. PER WPB FBC 107.2.1, |
| | PROVIDE TERMINATION FOR THE RELIEF VALVE DISCHARGE ON |
| | THE DETAIL. |
| | ***B) PER WPB FBC 107.2.1, PROVIDE T&P DISCHARGE PIPE |
| | SIZE AND MATERIAL |
| | ***C) PER WPB FBC 107.2.1, PROVIDE PAN DRAIN MATERIAL. |
| | PER FBC PL 504.7.1, PIPING MATERIAL FOR PAN DRAIN SHALL |
| | COMPLY WITH FBC PL TABLE 605.4. |
| | ***D) PER WPB FBC 107.2.1, PROVIDE THE TEMPERATURE OF |
| | THE HOT WATER SUPPLY TO THE FIXTURES. |
| | |
| | 23. PINK BIRD 2 CAR WASH EXPRESS INSTALLATION |
| | 2-24-22-02: EQUIPMENT OVERVIEW/LISTED EQUIPMENT |
| | INDICATES A COMPRESSED AIR SYSTEM. PER WPB FBC 107.2.1, |
| | PROVIDE PLAN VIEW AND RISER DIAGRAM SHOWING AND |
| | IDENTIFYING ALL COMPONENTS; PROVIDE MATERIAL |
| | SPECIFICATION. |
| | |
| | 24. PINK BIRD 2 CAR WASH EXPRESS INSTALLATION |
| | 2-24-22-02: PER WPB FBC 107.2.1 AND 107.2.1.2, PROVIDE |
| | PLAN VIEW/OVERVIEW AND SCHEMATIC/P&ID FOR ALL |
| | NON-POTABLE/PROCESS SYSTEMS; INCLUDE AND IDENTIFY ALL |
| | EQUIPMENT. RECONCILE WITH PINK BIRD 2 CAR WASH EXPRESS |
| | INSTALLATION 2-24-22-P1. |
| | |
| | 25. PER WPB FBC 107.2.1, RECONCILE P1 SANITARY PLAN AND |
| | PINK BIRD 2 CAR WASH EXPRESS INSTALLATION 2-24-22-C1 |
| | TRENCH PLAN AND ELEVATION SLEEVE/PIPING. |
| | |
| | 26. AS1, AS2 AND ES1 INDICATE A VACUUM SYSTEM; NOTHING |
| | IS INDICATED ON THE PLUMBING OR MECHANICAL PLANS. PER |
| | WPB FBC 107.2.1, CLARIFY. PER WPB FBC 105.1, A PERMIT |
| | IS REQUIRED. PER WPB FBC 107.2.1 AND 107.3.4, PROVIDE |
| | PLANS AND SPECIFICATIONS FOR THE SYSTEM INCLUDING ALL |
| | PIPING. |
| | |
| | 27. PER FBC PL 1301.3 & 1301.9.9, NON-POTABLE WATER |
| | SIGNAGE IS REQUIRED IN THE EQUIPMENT ROOM, OUTLETS AND |
| | AT ALL COMPONENTS OF THE RECLAIMED WATER SYSTEM. PER |
| | WPB FBC 107.2.1, PLEASE SHOW SIGN LOCATIONS AND PROVIDE |
| | SIGNAGE DETAILS. |
| | |
| | 28. PLEASE NOTE THAT IF THE BUILDING PLANS EXAMINER |
| | DETERMINES THAT THE PROPOSED BUILDING IS A FLOOD ZONE |
| | AREA, PROVISION SHALL BE MADE IN ACCORDANCE WITH FBC PL |
| | 309.2, 1301.9.3.1 AND FBC 1612. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |