| Plan Review Notes For Permit 22061065 |
| Permit Number |
22061065 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-14 06:55:42 | 1ST REVIEW FMC | | | PERMIT: 22061065 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FMC C403.2.1 | | | | | | 2) SHEET M-1; KEYNOTE 1 INDICATES THAT THE AHU SHALL BE | | | LOCATED IN THE PLENUM SPACE. KEYNOTE 2 INDICATES THE | | | CONDENSATE DRAIN IS TO BE PVC. PROVIDE A PLENUM RATED | | | MATERIAL FOR THE CONDENSATE DRAIN PIPE. FMC 602.2.1 | | | | | | 3) PROVIDE GUARD PROTECTION FOR THE SERVICING OF THE | | | CONDENSING UNIT LOCATED CLOSER THAN 10 FOOT FROM THE | | | ROOFS EDGE. FMC 304.11 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|