2022-07-14 06:55:421ST REVIEW FMC
 PERMIT: 22061065
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FMC C403.2.1
  
 2) SHEET M-1; KEYNOTE 1 INDICATES THAT THE AHU SHALL BE
 LOCATED IN THE PLENUM SPACE. KEYNOTE 2 INDICATES THE
 CONDENSATE DRAIN IS TO BE PVC. PROVIDE A PLENUM RATED
 MATERIAL FOR THE CONDENSATE DRAIN PIPE. FMC 602.2.1
  
 3) PROVIDE GUARD PROTECTION FOR THE SERVICING OF THE
 CONDENSING UNIT LOCATED CLOSER THAN 10 FOOT FROM THE
 ROOFS EDGE. FMC 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  