| 2022-07-28 16:26:35 | ELECTRICAL REVIEW FAILED |
| | 1) IT APPEARS THE POWER PLAN DRAWING, RISER, PANEL |
| | SCHEDULES AND THE EQUIPMENT DRAWING PROVIDED DO NOT |
| | MATCH. THE EQUIPMENT DRAWING DETAILS HIGH AND LOW HORSE |
| | POWER PANELS AND AN MCC CABINET. THE RISER AND POWER |
| | PLAN AND PANEL SCHEDULES ONLY DETAIL AN MCC. PLEASE |
| | CLARIFY AS APPLICABLE. NEC 215.5 |
| | 2) PLEASE PROVIDE SPECIFICATIONS FOR ALL OVERCURRENT |
| | AND OVERLOAD PROTECTION IN MCC CABINET. NEC 215.5 |
| | 3) PLEASE PROVIDE NOTES ON PLANS THAT SIGN, LOW |
| | VOLTAGE, FIRE ALARM, SECURITY, SITE LIGHTING AND ACCESS |
| | CONTROL WIRING REQUIRE SEPARATE PERMITS |
| | 4) PLEASE PROVIDE A LEGEND DETAILING THE EQUIPMENT |
| | NUMBERS ON THE POWER PLAN DRAWING. FBC 107.2 |
| | 5) PLEASE PROVIDE FAULT CURRENT CALCULATIONS AND FAULT |
| | CURRENT LETTER FROM FPL. NEC 110.9 |
| | 6) POWER PLAN DOES NOT DETAIL 150 480 VOLT DISCONNECT |
| | FEEDING TRANSFORMER. PLEASE CORRECT AS APPLICABLE. NEC |
| | 215.5 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |