| Date |
Text |
| 2022-08-05 10:46:51 | NEW BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) COPIES OF THE PRODUCT |
| | APPROVALS LISTED ON THE DRAWINGS FOR THE EXTERIOR |
| | WINDOWS, DOORS, ROOFING SYSTEMS, LOUVERS, ROOF HATCH |
| | ETC. |
| | |
| | 2) ACCESSIBLE RESTROOM = DRAWING A1B- DETAIL "C" SHOWS |
| | 6" FROM THE SIDE WALL TO THE EDGE OF THE REAR TOILET |
| | GRAB BAR AND 17" TO THE CENTER OF THE TOILET - THE MATH |
| | DOESN'T WORK WITH 12" FROM THE EDGE OF THE GRAB BAR TO |
| | THE CENTER OF THE TOILET. - FBC A 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 3) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS |
| | "REFLECTIVE SURFACE" WHEN REFERRING TO THE LOCATION |
| | DIMENSIONS FOR THE MIRROR - FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 4) ACCESSIBLE RESTROOM = THE ADDED VERTICAL GRAB BAR ON |
| | THE SIDE WALL NEXT TO THE TOILET IS NOT A REQUIREMENT |
| | OF THE FBC ACCESSIBILITY CODE - PLEASE SHOW THE 12" |
| | CLEARANCE ABOVE THE TOILET SIDE WALL GRAB PER FBC A |
| | 609.3 SPACING. THE SPACE BETWEEN THE GRAB BAR AND |
| | PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM) |
| | MINIMUM. |
| | |
| | 5) PLEASE PROVIDE CANOPY DETAILS - |
| | CANOPY DETAILS, ROOFING SYSTEMS, WINDOW AND DOOR |
| | PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING |
| | ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| | FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| | OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| | THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| | THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| | PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| | PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 6) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING |
| | BUILDING DEMO, DUMPSTER ENCLOSURE, VACUUME ENCLOSURE, |
| | PARKING LOT, PARKING LOT LIGHTING, FREE STANDING |
| | CANOPIES, VACUUME SYSTEM, SIGNS, FLAG POLE. PLEASE |
| | ACKNOWLEDGE THIS. |
| | |
| | |