Plan Review Notes
Plan Review Notes For Permit 22061055
Permit Number 22061055
Review Stop P
Sequence Number 1
Notes
Date Text
2022-07-20 09:24:131ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22061055
 7/20/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-1.01 & A-2.01: CHURCHES ARE EXEMPT FROM
 TITLE III ADA SEC. 36.102(E) AND THE FLORIDA
 ACCESSIBILITY CODE- 2020, HOWEVER AN ADA COMPLIANT
 SINGLE USER TOILET ROOM IS SHOWN ON THE PLAN. PLEASE
 PROVIDE THE FOLLOWING DETAILS PER THE FBC ACC:
 A) THE DIMENSIONS OF THE CLEAR FLOOR SPACE FOR THE
 WATER CLOSET- SEC. 604.3.
 B) THE DIMENSIONS OF THE CLEAR FLOOR SPACE FOR THE
 LAVATORIES- SEC. 606.2.
 C) THE DIAMETER OF THE TURNING SPACE- SEC. 304.3.
 D) HEIGHT OF THE MIRROR MEASURED FROM THE FINISHED
 FLOOR TO THE REFLECTIVE SURFACES- SEC. 603.3.
 E) SHOW THE 36-INCH LONG REAR WALL GRAB BAR EXTENDING
 FROM THE CENTERLINE OF THE WATER CLOSET 12 INCHES
 MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE OTHER
 SIDE- SEC. 604.5.2.
 F) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SEC. AND FIGURE
 604.7.
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 2) SHEETS A-1.01 & A-2.01: BASED ON COMMENT #1 ABOVE
 PLEASE CLARIFY THE DESIGN INTENTION FOR THE MEN'S AND
 WOMEN'S RESTROOMS. PLEASE NOTE IF COMPLIANCE WITH THE
 FBC ACC IS INTENDED THEN UNDER SEC. 213.2 FBC ACC THE
 CURRENT DESIGN IS NON-COMPLIANT. COMPLIANCE WOULD
 REQUIRE THE FOLLOWING CHANGES TO THE DESIGN PER SEC.
 213.2- 213.3.5.
 A) A MINIMUM OF ONE ACCESSIBLE WATER CLOSET COMPARTMENT
 IN EACH ROOM- SEC. 604.8.1.
 B) A MINIMUM OF ONE ACCESSIBLE LAVATORY IN EACH ROOM-
 SEC. 606.
 C) A MINIMUM OF ONE ACCESSIBLE MIRROR IN EACH ROOM-
 SEC. 603.3.
  
 D) A CLEAR FLOOR SPACE DIAGRAM IS SHOWN AT THE URINAL
 WHICH IMPLIES AN ACCESSIBLE URINAL IS TO BE INSTALLED.
 PLEASE PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR SPACE-
 SEC. 605.3, AND AN ELEVATION DETAIL SHOWING THE HEIGHT
 OF THE URINAL RIM- SEC. 605.2.
  
 3) A-1.01: PROVIDE THE DEPTH AND WIDTH MEASUREMENTS OF
 THE TOILET COMPARTMENTS IN THE WOMEN'S RESTROOM
 MEASURED IN THE WATER CLOSET LOCATIONS- SEC. 405.3.1
 FBC P.
  
 4) P0.1, P1.1, & P3.1: IT APPEARS THE 1/2-INCH HW LINE
 TO THE LAVATORY IN THE UNISEX ADA TOILET ROOM WILL BE
 EXCEEDING THE MAXIMUM 2FT. LENGTH FROM THE HW SOURCE-
 SEC. C404.5.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  