| 2022-07-15 08:39:00 | 1ST REVIEW FMC | | | PERMIT: 22061055 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) FMC 403.3.1.1 STATES: THE OCCUPANT LOAD UTILIZED FOR | | | DESIGN OF THE VENTILATION SYSTEM SHALL BE NOT LESS THAN | | | THE NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM | | | OCCUPANT LOAD RATE INDICATED IN TABLE 403.3.1.1. THE | | | OCCUPANT COUNT FOR THE PLACES OF WORSHIP MUST BE BASED | | | ON TABLE 403.3.1.1 AND NOT THE EGRESS OCCUPANT LOAD. | | | | | | 2) THE STORAGE AREAS MUST ALSO BE COUNTED IN THE | | | OUTDOOR AIR CALCULATIONS. FMC TABLE 403.3.1.1 | | | | | | 3) REMOVE THE BID ALTERNATES AND PROVIDE THE READY FOR | | | CONSTRUCTION DRAWINGS. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|