| 2022-08-20 09:27:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | SEE PREVIOUS LIST FOR CODE REFERENCES | | | | | | 2. THE FBC REQUIREMENT FOR FLAME SPREAD IS FOR THE | | | UNDERLAYMENT. APPLICANT UPLOADED A SPEC SHEET FOR | | | "KAHRS TECHNICAL DATA" WHICH APPEARS TO BE THE | | | FLOORING. IT STATES THAT THE ASTM E-84 FLAME SPREAD FOR | | | THIS PRODUCT IS 145. PLEASE SUBMIT THE ACTUAL TEST | | | REPORT AND I'LL TAKE THIS TO THE BUILDING OFFICIAL TO | | | SEE IF WE CAN ACCEPT THE TEST FOR THE FLOORING RATHER | | | THAN THE UNDERLAYMENT PER FBC 104.11 ALTERNATIVE | | | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION. |
|