Plan Review Notes
Plan Review Notes For Permit 22061052
Permit Number 22061052
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-23 18:47:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, PROVIDE A PLAN SHOWING PROPOSED AREA OF
 WORK.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FLAME
 SPREAD TEST. THE TESTS WE HAVE ON FILE ARE FOR TILE,
 WOOD FLOOR IS PROPOSED.
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  