Plan Review Notes
Plan Review Notes For Permit 22061018
Permit Number 22061018
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-24 09:01:22WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. SUBMITTAL: 22061018
 W. P. B. PERMIT: 21070509
 ADD: 2751 S. DIXIE HWY.
 CONT: RED DOOR
 TEL: 786-535-1006
 E-MAIL: HANS@REDDOOR CONSTRUCTION.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 6/17/22 APPLICANT INVITED TO UPLOAD PLANS.
 10/07/2022 PLANS UPLOADED, INCOMING COMPLETE.
  
 ACTION: DENIED
  
 1) SHEET LABELED E30, A MECHANICAL SHEET FOR CONDENSING
 UNIT STAND. THE ELEVATION VIEW SHOWS A ELEVATION OF 2
 FEET FROM THE BOTTOM OF THE A/C CONDENSING UNIT. THE
 ELEVATION SHOWS A HORIZONTAL FRAMING UNIT W8X10 STEEL
 BEAM. IN THE 2020 FBC-BUILDING CODE SECTION 1510.10 &
 TABLE 1510.10 BOTH STATE A MINIMUM CLEARANCE HEIGHT.
 THIS HEIGHT IS NOT FROM THE BOTTOM OF THE CONDENSATE
 UNIT BUT THE LOWEST HORIZONTAL FRAMING MEMBER. THIS IS
 A SPECIFIC FLORIDA REQUIREMENT, IT IS NOT COVERED UNDER
 THE IBC- BASE CODE. FROM THE 2007 FBC-BUILDING
 COMMENTARY IT STATES: BY HAVING THE ROOF MOUNTED
 EQUIPMENT RAISED TO PROVIDE ACCESS TO THE ROOF COVERING
 UNDER THE EQUIPMENT, THE ROOF MOUNTED EQUIPMENT AND
 ROOF COVERING CAN BE MAINTAINED INDEPENDENTLY OF EACH
 OTHER.
 PLEASE NOTE ROOF SLOPES, ROOF TOP INSULATION AND FINISH
 ROOFING PRODUCT NEED TO BE CONSIDERED WHEN TRYING TO
 MAINTAIN A MINIMUM CLEARANCE OF 2 FEET FROM FINISH ROOF
 DECK AND THE BOTTOM FLANGE OF THE HORIZONTAL FRAMING
 MEMBER FOR THE 3 FEET 7 ?? INCH WIDE CENTER LINE /
 CENTER LINE WIDTH STAND.
 WILL REQUIRE NEW CALCULATIONS FOR THE NEW HEIGHT OF THE
 STAND.
  
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  