| 2023-01-31 10:42:06 | 4TH REVIEW FMC |
| | PERMIT: 22061010 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS |
| | NOW INDICATED BARBER SHOP. THE PREVIOUS SUBMITTAL DID |
| | SHOW MANICURE STATIONS. FMC TABLE 403.3.1.1 |
| | |
| | 2) THE REVIEWER NOTES SUBMITTED THIS CYCLE HAS A |
| | MECHANICAL REVIEW DATE OF 08/08/2022, THIS IS NOT THE |
| | MOST RECENT REVIEW COMMENTS. THE MOST RECENT MECHANICAL |
| | REVIEW COMMENTS ARE DATED 1/12/2023 AND THERE ARE 6 |
| | COMMENTS THAT WOULD NEED TO BE ADDRESSED. PLEASE SEE |
| | BELOW: |
| | 3RD REVIEW FMC |
| | PERMIT: 22061010 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I CANNOT DO A COMPLETE REVIEW UNTIL A COMPLETE |
| | DESIGN FOR THIS TENANT IS DESIGNED AND SUBMITTED. |
| | |
| | 2) THE PERMIT APPLICATION SHOULD REFLECT WHAT IS BEING |
| | BROUGHT INTO THIS TENANT SPACE. CORRECT THE |
| | APPLICATION. |
| | |
| | 3) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS NEW |
| | TENANT. THE UPSTAIRS WAS FOR THE LIVE AND THE MAIN |
| | FLOOR WAS FOR THE BUSINESS. IT APPEARS THAT NOW THE |
| | ENTIRE TENANT SPACE IS TO BE A BEAUTY SALON WITH |
| | MANICURE STATIONS. THIS REQUIRES MORE EXHAUST THAN THE |
| | ORIGINAL DESIGN OF THIS SPACE HAS NOW. FBC 107.3.5 |
| | |
| | PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THIS CHANGE |
| | OF USE. PROVIDE A COMPLETE EXHAUST DESIGN FOR THE |
| | MANICURE STATIONS. IS THERE TO BE PEDICURE STATIONS AS |
| | WELL? IF SO SHOW THE DESIGN FOR THIS AS WELL. |
| | 502.20 MANICURE AND PEDICURE STATIONS. MANICURE AND |
| | PEDICURE STATIONS SHALL BE PROVIDED WITH AN EXHAUST |
| | SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1, NOTE H. |
| | MANICURE TABLES AND PEDICURE STATIONS NOT PROVIDED WITH |
| | FACTORY-INSTALLED EXHAUST INLETS SHALL BE PROVIDED WITH |
| | EXHAUST INLETS LOCATED NOT MORE THAN 12 INCHES (305 MM) |
| | HORIZONTALLY AND VERTICALLY FROM THE POINT OF CHEMICAL |
| | APPLICATION. |
| | |
| | 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE ENTIRE |
| | TENANT SPACE FOR EACH USE OF SPACE. USE THE OCCUPANCY |
| | CLASSIFICATION FROM TABLE 403.3.1.1 FOR THE OCCUPANCY |
| | USE OF EACH SPACE. |
| | |
| | 5) THE UPSTAIRS BATHROOM APPEARS TO NOW BE FOR THE |
| | PUBLIC. SHOW THAT THE BATHROOM EXHAUST FAN WILL MEET |
| | THE EXHAUST REQUIREMENTS FROM TABLE 403.3.1.1 |
| | |
| | 6) THE NEW O/A GRILL APPEARS TO BE COMING FROM THE A/C |
| | CLOSET. HOW IS THIS OUTDOOR AIR BEING CONDITIONED? |
| | TYPICALLY, THE OUTDOOR AIR IS BROUGHT INTO THE RETURN |
| | AIR DUCT AT THE MECHANICAL SYSTEM FROM THE EXTERIOR OF |
| | THE BUILDING. SHOW THE DUCT SIZE ON THE DRAWING FOR THE |
| | OUTDOOR AIR. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |