Plan Review Notes
Plan Review Notes For Permit 22061002
Permit Number 22061002
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-22 10:35:23FIRE PROVISO COMMENTS:
 ALL LIFE SAFETY SYSTEMS THAT ARE APPLICABLE (FIRE ALARM
 AND/OR FIRE SPRINKLER) SHALL REMAIN ACTIVE DURING
 DEMOLITION.
 ANY IMPAIRMENT TO A LIFE SAFETY SYSTEM (FIRE ALARM
 AND/OR FIRE SPRINKLER) IN EXCESS OF 4 CONTINUOUS HOURS
 DURATION SHALL HAVE A FIRE WATCH IMPLEMENTED.
 ALL FIRE AND LIFE SAFETY SYSTEMS (FIRE ALARM AND/OR
 FIRE SPRINKLER) SHALL BE PROTECTED FROM DAMAGE DURING
 DEMOLITION.
 WITH THE REMOVAL OF WALLS, AN EVALUATION OF ALL
 APPLICABLE LIFE SAFETY SYSTEMS (FIRE ALARM AND/OR FIRE
 SPRINKLER) SHALL BE CONDUCTED BY PROPERLY LICENSED
 CONTRACTORS TO ENSURE CODE COMPLIANT COVERAGE.
  