Plan Review Notes
Plan Review Notes For Permit 22060989
Permit Number 22060989
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-07-20 10:42:56FAILED
  
 REVISED SHEET M-101 INCLUDES NEW NOTE HV9 THAT STATES A
 CONDENSING UNIT WILL BE PROVIDED ON THE ROOF. PROVIDE A
 ROOF PLAN SHOWING WHERE THIS UNIT IS TO BE INSTALLED AS
 WELL AS A CROSS-SECTION THAT VERIFIES THAT THE NEW
 ROOFTOP CONDENSING UNIT IS SCREENED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE CITYPLACE DRI.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]