| Plan Review Notes For Permit 22060972 |
| Permit Number |
22060972 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-29 08:20:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. FBC R 310.4, REVISE PLAN TO SHOW EMERGENCY ESCAPE | | | OPENING. THE PLAN SHOWS THAT THE FRONT DOOR WILL BE | | | COVERED. IT IS NOT CLEAR IF THE DOOR WILL REMAIN | | | OPERABLE. IF YES, NOTE ON PLAN. IF NO, INDICATE THE | | | OPENING ON THE PLAN. | | | | | | 3RD REVIEW: | | | | | | NOTHING WAS NOTED ON THE SITE PLAN. THE PLAN SHOWS TWO | | | OPENINGS TO BE COVERED - NO 1, A RECESSED DOOR. NO 2, | | | ANOTHER OPENING THAT IS MARKED "FRONT ENTRY". SEE THE | | | PRODUCT APPROVAL FL812.1, SHEET 3 OF 9. SOMEONE CIRCLED | | | A DETAIL WHICH APPEARS TO PROPOSE INSTALLATION FROM THE | | | TRUSS TO THE FOOTER. THEREFORE IT APPEARS THAT EXITING | | | FROM THE RECESSED DOOR IS OBSTRUCTED. | | | | | | REVISE PLAN TO SHOW THE EMERGENCY ESCAPE OPENING. THIS | | | CAN BE ANOTHER OPENING IN THE HOUSE. INCLUDE THE ROOM | | | DESIGNATION. | | | | | | 2. NEW COMMENT - INSTALLATION SCHEDULE PROPOSES | | | HORIZONTAL INSTALLATION INTO CONCRETE. THIS IS IN | | | CONFLICT WITH THE DETAIL CIRCLED ON SHEET 3. FBC 107, | | | CLARIFY. | | | |
|