| 2022-11-03 14:11:53 | 1. THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO |
| | THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH |
| | THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED |
| | WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS |
| | BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS |
| | WELL AS WITH THIS PERMIT. |
| | WCF 21120287 FAILED ZONING REVIEW ??? 1/3/22 |
| | - PLEASE ALIGN POLE WITH EXISTING STREET TREE/PALMS. |
| | ANTENNA POLE COLOR SHALL BE ANALOGOUS TO THE EXISTING |
| | DECORATIVE CITY STREET LAMPS (RAYCAP RAL 7022 UMBRA |
| | GREY). |
| | |
| | - PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE |
| | DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS RELATIVE |
| | TO EXISTING UNDERGROUND UTILITIES AND LINES. |
| | |
| | - UNDERGROUND ELECTRIC SHOWN ON DRAWINGS MAY CONFLICT |
| | WITH EXISTING SANITATION/SEWER LINE, COMMUNICATIONS |
| | LINE, AND WATER; PLEASE PROVIDE THE NECESSARY PUBLIC |
| | UTILITY LETTERS GRANTING APPROVAL OF THE PROPOSED BORE |
| | PITS, UNDERGROUND ELECTRIC, AND POLE LOCATIONS. |
| | |
| | - THE POLE STEALTH DESIGN MEETS CITY STANDARDS. |
| | |
| | 2. POLE COLOR TO BE RAYCAP RAL 7022 (UMBRA GREY) |
| | |
| | 3. POWER PULLED FROM LOCATION OUTSIDE OF ROW AND WITHIN |
| | PRIVATE PROPERTY. PLAN SHEETS AND SURVEY ALSO SUGGEST |
| | PRIVATE PROPERTY, PLEASE PROVIDE PROOF OF WORK BEING |
| | DONE WITHIN GENERAL UTILITY EASEMENT, IN ORDER TO PULL |
| | POWER FROM THIS LOCATION. OTHERWISE POWER MUST BE |
| | OBTAINED FROM ANOTHER SOURCE. |
| | |
| | |