| 2022-11-03 14:01:41 | 1. THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO |
| | THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH |
| | THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED |
| | WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS |
| | BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS |
| | WELL AS WITH THIS PERMIT. |
| | WCF 21120300 FAILED ZONING REVIEW ??? 1/5/22 |
| | - SITE SURVEY (B-1) IS MISSING AN ADDITIONAL OVERHEAD |
| | WOODEN DISTRIBUTION POLE, DIRECTLY ADJACENT TO THE POLE |
| | WHERE THE PROPOSED ELECTRICAL HOOKUP TAKES PLACE. |
| | PLEASE ADJUST SITE SURVEY AND DRAWINGS TO ACCURATELY |
| | REFLECT CURRENT SITE CONDITIONS. |
| | |
| | - CONCRETE CAISSON IS SHOWN ON SURVEY TO CONFLICT WITH |
| | EXISTING GAS LINE, PLEASE PROVIDE THE NECESSARY PUBLIC |
| | UTILITY LETTER GRANTING APPROVAL OF THIS PROPOSED POLE |
| | LOCATION AND DEPTH. |
| | |
| | - POLE & UNDERGROUND ELECTRIC SHOWN ON DRAWINGS TO |
| | CONFLICT WITH EXISTING GAS LINES, PLEASE PROVIDE THE |
| | NECESSARY PUBLIC UTILITY LETTERS GRANTING APPROVAL OF |
| | THIS PROPOSED BORE PITS, UNDERGROUND ELECTRIC, AND POLE |
| | LOCATIONS. |
| | |
| | - PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE |
| | DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS. |
| | |
| | - THE POLE STEALTH DESIGN MEETS CITY STANDARDS. |
| | |
| | 2. POLE COLOR TO BE RAYCAP RAL 7022 (UMBRA GREY) |
| | |
| | |
| | CHRIS KIMMERLY, AICP |
| | URBAN DESIGN PLANNER |
| | [email protected] 822-1426 |
| | |