| Plan Review Notes For Permit 22060901 |
| Permit Number |
22060901 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-29 11:51:11 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING SP1.01 - THE SCOPE OF WORK AND THE BUILDING | | | SQUARE FOOTAGE ARE SHOWN FOR THE ACCESSORY BUILDING - | | | PLEASE SHOW BUILDING SQUARE FOOTAGE FOR THE HOUSE AC | | | SPACE, GARAGE, PATIOS ETC. - FBC WPB 107 | | | | | | 2) UNABLE TO FIND THE TRUSS STRAPPING LOCATIONS ON THE | | | STRUCTURAL ROOF DRAWINGS - | | | | | | 3) PLEASE PROVIDE THE PRODUCT APPROVAL LISTED ON THE | | | ARCHITECTS APPROVED PRODUCT APPROVAL LIST FOR THE | | | SHUTTERS AND THE OVERHEAD DOOR. FBC WPB 107 | | | | | | 4) PRODUCT APPROVAL FL17017-R5 CASEMENT WINDOW - PLEASE | | | INCLUDE ALL OF THE INSTALLATION INSTRUCTIONS WHICH AR | | | PART OF THE PRODUCT APPROVAL. | | | | | | 5) PRODUCT APPROVAL FL14939-R13 DOUBLE HUNG WINDOW - | | | PLEASE INCLUDE ALL OF THE INSTALLATION INSTRUCTIONS | | | WHICH AR PART OF THE PRODUCT APPROVAL. | | | |
|