| Plan Review Notes For Permit 22060892 |
| Permit Number |
22060892 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-10-05 17:04:08 | 10/05/22 TALKED TO ANDERSON BAXAM. EXPLAINED TO HIM | | | THAT 3' PARAPET AROUND ROOF QUALIFY FOR DESIGN | | | PRESSURES ON ZONE #3 CAN BE THE SAME AS ZONE #2. (ASCE | | | 7-16). TOLD HIM, THE DESIGN PRESSURES ON ZONE #2 ARE | | | HIGHER THAN -60PSF. THEREFORE, ANOTHER ASSEMBLY NEEDS | | | TO BE SELECTED. ALSO, INFORMED HIM ABOUT FLORIDA | | | PRODUCT APPROVAL FL16709 WHICH HAS ENGINEERING | | | INCORPORATED. JG. | | | | | | | | | | | | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22060892 | | | 813 35TH ST | | | | | | 1-CERTAINTEED MODIFIED BITUMEN ROOFING SYSTEM NOA | | | 20-0723.29 SUBMITTED: | | | SELECTED ASSEMBLY MAXIMUM DESIGN PRESSURE (-60PSF) ON | | | PAGE 31 OF 48 DOESN'T MEET THE DESIGN PRESSURE FOR ALL | | | ROOF ZONES. NEED TO SELECT ANOTHER ASSEMBLY THAT MEETS | | | THE DESING PRESSURES FOR ALL ROOF ZONES OR PROVIDE | | | SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY | | | GENERAL LIMITATION ON LAST PAGE OF NOA SUBMITTED. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|