| Plan Review Notes For Permit 22060872 |
| Permit Number |
22060872 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-23 10:56:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FS553, FBC BUILDING, THIS IS A CONDOMINIUM. | | | ARCHITECT ON PAGE A101 STATES THIS IS R3, RESIDENTIAL | | | CODE, TYPE V BUILDING TYPE. ARCHITECT ALSO STATES THAT | | | GOVERINING CODE IS FBC RESIDENTIAL, THIS IS NOT CORRECT | | | AS THIS IS NOT A ONE-OR-TWO-FAMILY DWELLING. | | | | | | AN ACCURATE REVIEW CANNOT BE DONE WITHOUT DETERMINING | | | BUILDING TYPE AND OCCUPANCY CLASSIFICATION PER FBC | | | BUILDING. THIS IS A CONDOMINIUM WHICH IS R2 OCCUPANCY. | | | BUILDING TYPE V DOES NOT APPEAR TO BE CORRECT, PLEASE | | | CONFIRM AND IF IT REMAINS TYPE V, INCLUDE A STATEMENT | | | AS TO HOW THIS HAS BEEN DETERMINED, (SUCH AS BUILDING | | | PLANS FROM ORIGINAL BUILDING PERMIT ISSUANCE). | | | | | | 2. S101, ARCHITECT STATES WIND DESIGN CRITERIA AS | | | ASCE10-05, EXPOSURE B, 170MPH. ASCE REFERENCE NOT | | | CORRECT, EXPOSURE NOT CORRECT, NOTE THE PROXIMITY TO | | | THE LAKE, PLEASE REVISE. | | | | | | 3. FBC 107 CLARIFY SCOPE. APPLICATION IS FOR | | | INSTALLATION OF PT LUMBER, PLAN AND SPECS SHOW FIBERON | | | DECKING. | | | | | | | | | | | | |
|