| 2022-08-03 13:51:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 2ND REVIEW - THE STC AND IIC TEST REPORTS WERE DONE |
| | WITH A DROPPED CEILING AND AN 8" SLAB. OUR RECORDS SHOW |
| | THAT THS BUILDING HAS A 5.5" SLAB, SO YOU NEED A |
| | PRODUCT THAT HAS BEEN TESTED TO A 6" OR THINNER SLAB. |
| | |
| | PROFLEX MSC 90 IS PROPOSED. WE DO NOT HAVE TEST REPORTS |
| | ON FILE, PLEASE PROVIDE. |
| | |
| | PROFLEX SUPERSIM 90 FLAME SPREAD TEST WAS UPLOADED. IF |
| | YOU WISH TO USE THAT PRODUCT, PLEASE ADVISE, WE HAVE |
| | TEST REPORTS ON FILE. WHEN RESUBMITTING PLEASE SUBMIT A |
| | RESPONSE LETTER MAKING THIS REQUEST. IF NOT, PLEASE |
| | PROVIDE THE STC AND ICC TESTS AS NOTED ABOVE. |
| | |
| | 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED |
| | UNDERLAYMENT STC, IIC, FLAME SPREAD: |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | |