| 2022-07-26 11:43:29 | 1ST REVIEW FMC |
| | PERMIT: 22060835 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT NOT |
| | THE INSPECTION CHECKLIST FOUND ON SHEET M3.01. FBC |
| | 101.5.1.1.2 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 3) PROVIDE DETAIL DRAWING OF THE MANICURE/PEDICURE |
| | STATIONS MEETING THE REQUIREMENTS OF FMC 502.20: |
| | MANICURE AND PEDICURE STATIONS SHALL BE PROVIDED WITH |
| | AN EXHAUST SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1, |
| | NOTE H. MANICURE TABLES AND PEDICURE STATIONS NOT |
| | PROVIDED WITH FACTORY-INSTALLED EXHAUST INLETS SHALL BE |
| | PROVIDED WITH EXHAUST INLETS LOCATED NOT MORE THAN 12 |
| | INCHES (305 MM) HORIZONTALLY AND VERTICALLY FROM THE |
| | POINT OF CHEMICAL APPLICATION. |
| | |
| | 4) SHEET M2.01: PROVIDE THE OUTDOOR AIR CALCULATIONS |
| | ACCORDING TO THE OCCUPANCY CLASSIFICATION FROM TABLE |
| | 403.3.1.1. HALLS AND LOBBIES HAVE DIFFERENT |
| | CALCULATIONS. |
| | |
| | 5) SHEET M1.02: EXPLAIN THE USE OF THE SUPPLY DUCT |
| | GOING INTO THE WATER HEATER CLOSET. FBC 107.2.1 |
| | |
| | 6) REMOVE THE RETURN AIR GRILLES FROM THE UTILITY ROOM. |
| | FMC 601.5 |
| | |
| | 7) M1.02: PROVIDE THE DRYER DUCT MATERIAL, SIZE AND |
| | MATERIAL. FMC 504. |
| | |
| | 8) EF-4 A,B,C,D: MUST MEET FMC 504.5. PROVIDE THE |
| | SPECIFICATIONS FOR THESE EXHAUST FANS THAT SHOWS THE UL |
| | 705 LISTING ALONG WITH THE INSTALLATION INSTRUCTIONS |
| | SHOWING THE APPROVED LENGTHS THE DUCT WORK; DRYER |
| | EXHAUST DUCT POWER VENTILATORS. DOMESTIC DRYER EXHAUST |
| | DUCT POWER VENTILATORS SHALL BE LISTED AND LABELED TO |
| | UL 705 FOR USE IN DRYER EXHAUST DUCT SYSTEMS. THE DRYER |
| | EXHAUST DUCT POWER VENTILATOR SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| | |
| | 9) THE GAS RISER DIAGRAM INDICATES ONLY 3 GAS DRYERS. |
| | SHEET M1.04 INDICATES 4 DRYER EXHAUST DUCTS. PLEASE |
| | EXPLAIN. FBC 107.2.1 |
| | |
| | 10) SHEET M1.04: EF-1 INDICATES PULLING EXHAUST FROM |
| | ABOVE THE CEILING? PLEASE EXPLAIN THE USE OF EF-1. FBC |
| | 107.2.1 |
| | |