2022-08-19 11:29:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS APPEAR TO BE MISSING SOME OF THE REQUIRED
 (DIRECTIONAL) EXIT SIGNS. 1013.1 WHERE REQUIRED. EXITS
 AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED
 EXIT SIGN READILY VISIBLE FROM ANY DIRECTION OF EGRESS
 TRAVEL. THE PATH OF EGRESS TRAVEL TO EXITS AND WITHIN
 EXITS SHALL BE MARKED BY READILY VISIBLE EXIT SIGNS TO
 CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL IN
 CASES WHERE THE EXIT OR THE PATH OF EGRESS TRAVEL IS
 NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS. INTERVENING
 MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE MARKED BY
 EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS
 MORE THAN 100 FEET (30 480 MM) OR THE LISTED VIEWING
 DISTANCE FOR THE SIGN, WHICHEVER IS LESS, FROM THE
 NEAREST VISIBLE EXIT SIGN.
  
 2) THE COMMON PATH OF EGRESS TRAVEL DISTANCE ON LIFE
 SAFETY SHEET A003 IS NOT SHOWN CORRECTLY. THE COMMON
 PATH OF EGRESS TRAVEL DISTANCE IS USED TO DETERMINE IF
 MORE THAN ONE EXIT IS REQUIRED. IT IS THE DISTANCE FROM
 THE MOST REMOTE POINT IN THE AREA TO AN EXIT OR TO
 WHERE THERE IS TWO SEPARATE AND DISTINCT PATHS OF
 TRAVEL TO SEPARATE EXITS. THE MAXIMUM COMMON PATH OF
 TRAVEL DISTANCE FOR A BUSINESS OCCUPANCY IN A FULLY
 SPRINKLERED BUILDING IS 100 FEET PER FBC TABLE
 1006.2.1. FBC 1006.2.1 EGRESS BASED ON OCCUPANT LOAD
 AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO EXITS OR
 EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED
 WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF
 EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN
 TABLE 1006.2.1. THE CUMULATIVE OCCUPANT LOAD FROM
 ADJACENT ROOMS, AREAS OR SPACES SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1004.2. FBC 202 DEFINITIONS.
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT
 ACCESS TRAVEL DISTANCE MEASURED FROM THE MOST REMOTE
 POINT OF EACH ROOM, AREA OR SPACE TO THAT POINT WHERE
 THE OCCUPANTS HAVE SEPARATE AND DISTINCT ACCESS TO TWO
 EXITS OR EXIT ACCESS DOORWAYS.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE PROPOSED WINDOWS
 AND LOUVERS IN THE EXTERIOR WALL THAT MEET THE REQUIRED
 COMPONENT AND CLADDING PRESSURES. FBC 107.3.4 - PROVIDE
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED.
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.