| Date |
Text |
| 2022-07-11 12:05:36 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1 SUBMITTED MIAMI-DADE COUNTY NOA 21-0609.09COVERS |
| | MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH F(5). |
| | SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED |
| | CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS AN |
| | EXPOSURE CATEGORY C AREA. |
| | 2. SUBMITTED MIAMI-DADE COUNTY NOA 21-0609.07 COVERS |
| | MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH F(12). |
| | SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED |
| | CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS AN |
| | EXPOSURE CATEGORY D AREA. |
| | 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL12772-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT). |
| | 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL12772-R9 COVERS MULTIPLE ROOF SYSTEMS; |
| | SYSTEM NO. W-1 THRU R-9. PLEASE SELECT SYSTEM NO. THAT |
| | MEETS OR EXCEEDS EXPOSURE CATEGORY C ZONE 3 DESIGN |
| | PRESSURE REQUIREMENTS OR PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATION FOR ZONE 3. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 5. FBC B 107.2.1. PLEASE CLARIFY: REFERENCE HAS BEEN |
| | MADE FOR MULTIPLE LOW SLOPE ROOF SYSTEMS; MIAMI-DADE |
| | COUNTY NOA NO.21-0609.09, MIAMI-DADE COUNTY NOA NO. |
| | 21-0609.07 AND PRODUCT APPROVAL FL12772-R9. PLEASE |
| | COMPLETE THE INSTRUCTIONS FOR THE PRODUCT APPROVAL/NOA |
| | TO BE USED AND RESUBMIT; IF USING MULTIPLE SYSTEMS |
| | PLEASE INDICATE ON ROOF SKETCH WHICH AREAS TO RECEIVE |
| | EACH SYSTEMS. |
| | 6. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| | SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| | NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| | PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| | INDICATE ON ROOF DRAWING/SKETCH). |
| | 7. FBC B 107.2.1 1 PROVIDE AN AERIAL MAP OF THE ENTIRE |
| | COMPLEX WITH EACH BUILDING CLEARLY IDENTIFIED BY |
| | NUMBER/LETTER TO BE REROOFED. |
| | 8. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| | MEAN ROOF HEIGHT(S). PROVIDE FOR EACH BUILDING TO BE |
| | REROOFED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |