| 2022-09-07 17:57:57 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22060780 |
| | 9/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A601 & P3: THE NEW ACCESSIBLE ROLL-IN SHOWER |
| | IS NOT DESIGNED IN COMPLIANCE WITH SEC. AND FIGURE |
| | 608.2.2. FBC ACC. A MINIMUM 60-INCH WIDE OPENING IS |
| | REQUIRED ON THE FACE OF THE COMPARTMENT, A MINIMUM |
| | 30-INCHES WIDE X 60 INCHES LONG CLEAR FLOOR SPACE SHALL |
| | BE PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER |
| | WHICH CANNOT BE OBSTRUCTED BY THE WATER CLOSET- SEC. |
| | 2.2.1 FBC ACC. UNDER THE EXCEPTION A LAVATORY COMPLYING |
| | WITH SEC. 606 SHALL BE PERMITTED ON ONE 30-INCH WIDE |
| | MINIMUM SIDE OF THE CLEARANCE PROVIDED IT IS NOT ON THE |
| | SIDE OF THE CLEARANCE ADJACENT TO THE CONTROLS- SEC. |
| | 606.2.2.1 FBC ACC. |
| | |
| | 2) A600 & A601: PROVIDE ACCESSIBLE GRAB BAR AND CONTROL |
| | DETAILS FOR THE NEW ROLL-IN SHOWER IN ACCORDANCE WITH |
| | SEC. & FIGURE 608.3.2, AND SEC. AND FIGURE 608.5.2 FBC |
| | ACC. |
| | |
| | 3) A100: THE DRINKING FOUNTAINS IN UNIT B ARE |
| | PROTRUDING INTO THE CIRCULATION PATH GREATER THAN THE |
| | MAXIMUM 4-INCHES ALLOWABLE PER SEC. 307.2 FBC ACC. |
| | PLEASE NOTE THAT DRINKING FOUNTAINS WITH CANE APRONS |
| | ARE ALLOWED HOWEVER THE FOUNTAINS WERE NOT INCLUDED IN |
| | THE FIXTURE SCHEDULE ON SHEET P-1. |
| | |
| | 4) P-1: THE WATER RISER SHOWS THE IWH-1 WATER HEATERS |
| | SUPPLYING LAVATORIES IN UNIT A AND UNIT C WHICH ARE |
| | REQUIRED TO DELIVER TEMPERED WATER, NOT HOT WATER- SEC. |
| | 419.5 FBC P. PLEASE PROVIDE ASSE 1070 APPROVED MIXING |
| | VALVES AT THE LOCATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |