| Plan Review Notes For Permit 22060780 |
| Permit Number |
22060780 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-09-08 11:34:42 | OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) CONSTRUCTION SHOWN IS TYPE II - PLEASE REMOVE THE | | | WOOD FRAMING WALLS FROM DRAWING A500 FBC 603.1 | | | | | | 2) PLEASE SHOW THE RESTROOM WALLS, SHOWER WALLS AND | | | WALL SURROUNDING THE SERVICE SINK TO COMPLY WITH FBC | | | 1210 - (DRYWALL IS NOT CONSIDERED A HARD SURFACE) | | | | | | 3) ACCESSIBLE ROLL IN SHOWER - I DO NOT SEE A SEAT | | | THEREFORE THE SIDE GRAB BAR SHOULD EXTEND FULL LENGTH | | | OF THE WALL PER FBC A FIGURE 608.5.3 | | | | | | | | | | | | | | | | | | |
|