Plan Review Notes
Plan Review Notes For Permit 22060780
Permit Number 22060780
Review Stop P
Sequence Number 1
Notes
Date Text
2022-06-27 11:15:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22060780
 6/27/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A100: THE FIXTURE CALCULATIONS SHALL BE
 CALCULATED FOR EACH OCCUPANCY SEPARATELY- SEC. AND
 TABLE 403.1 FBC P. BASED ON TABLE 403.1 FOOTNOTE(E),
 AND SEC. 410.2 SERVICE SINKS AND DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR UNITS A & B. PLEASE REVISE THE
 PLANS TO SHOW THE FIXTURE LOCATIONS AND PLUMBING PIPING
 DETAILS- SEC. 107.2.1 WPB.
  
 A) CONCERNING THE REQUIRED DRINKING FOUNTAINS, A
 MINIMUM OF TWO ARE REQUIRED PER SEC. 211.2 FBC ACC- ONE
 HI AND ONE LO FOR EACH UNIT. REFER TO SECTIONS 306,
 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 2) A100 & P3: PLEASE IDENTIFY THE BATHROOMS AS EITHER
 MALE, FEMALE, OR UNISEX- SECS. 403.2 & 403.4 FBC P.
  
 3) A100 & A600: THE GENERIC ACCESSIBLE STALL DETAILS ON
 A600 DO NOT REFLECT THE ACTUAL BATHROOM LAYOUTS PLANS
 FOR THE ACCESSIBLE BATHROOMS IN EACH UNIT. PROVIDE
 ENLARGED SITE-SPECIFIC ACCESSIBLE TOILET ROOM DRAWINGS
 FOR EACH UNIT SHOWING THE FOLLOWING LIST OF FBC ACC
 COMPLIANCES:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 4) A100 & A600: THE SHOWERS SHOWN IN BR2 & BR5 SHALL BE
 ACCESSIBLE IN ACCORDANCE WITH SEC. 213.3.6 FBC ACC.
 REVISE THE DRAWINGS TO PROVIDE THE FOLLOWING LIST OF
 FBC ACC COMPLIANCES:
 A) DIMENSIONS OF THE SHOWER- SEC. 608.2.1
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.1
 C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SEC. 608.3 AND 608.3.1
 D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SEC. 608.5.1.
 E) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6.
 F) LOCATION OF ACCESSIBLE SHOWER SEAT- SECS. 610.3 &
 610.3.2.
  
 5) A100 & A600: THE KITCHEN SINKS AND APPLIANCES SHOWN
 IN UNITS A & C SHALL BE ACCESSIBLE IN ACCORDANCE WITH
 SECS. 212.1 & 212.2 FBC ACC. PROVIDE ENLARGED DRAWINGS
 SHOWING THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE SINKS AND APPLIANCES- SEC. 606.2 & 804.1.
  
 6) P-1: IWH-2 SHALL PROVIDE HOT WATER, NOT TEMPERED
 WATER TO THE KITCHEN SINKS AND DISHWASHERS- SEC. 607.1
 FBC P.
  
 7) P-1: PROVIDE A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE FROM THE KITCHEN SINKS AND
 DISHWASHERS- SEC. 607.1.1 FBC P.
  
 8) P-1 & P-3: THE 1/2-INCH HW PIPES SUPPLYING THE
 LAVATORIES HAVE EXCEEDED THEIR MAXIMUM ALLOWABLE 2FT.
 LENGTHS FROM THE IWH-1 SOURCES- TABLE C404.5.1 FBC EC.
  
 9) P1: PROVIDE THE TYPE OF BACKFLOW PREVENTER TO BE
 INSTALLED- SEC. 608.3 FBC P AND SECS. C, D, & E WPB
 CROSS CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED FOR INSTALLATION OF THE DEVICE- SECS. 105.1
 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  