| 2022-07-08 07:33:27 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | (1) OUTLET SPACING AND FLOOR OUTLETS MISING IN BOTH |
| | CONFERENCE ROOMS PER 210.71 |
| | |
| | 210.71(B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER |
| | OF RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND |
| | RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE |
| | LESS THAN AS DETERMINED IN (1) AND (2). THESE |
| | RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS |
| | DETERMINED BY THE DESIGNER OR BUILDING OWNER. |
| | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE |
| | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | 210.52(A)(1) THROUGH (A)(4). |
| | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT |
| | LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF |
| | AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE |
| | RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE |
| | NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH |
| | 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE |
| | |
| | (2) AIC CALCULATION FOR THE SERVICE AND PANELS. 110.10 |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; |
| | |
| | (3) ALL KITCHEN OUTLETS TO BE GFCI PROTECTED PER |
| | 210.8(B) |
| | |
| | 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 |
| | AMPERES OR LESS AND THREEPHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100 |
| | AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS |
| | SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL. |
| | |
| | (4) VALUE OF PERMIT SEEMS LOW FOR THE AMOUNT OF WORK |
| | SHOWN ON PLANS.(18K) |
| | |
| | PLEASE SUBMIT A COST BREAKDOWN OR IF YOU WANT YOU CAN |
| | SUBMIT A SIGNED CONTRACT WITH THE OWNER. |