| 2022-10-04 11:54:40 | PLEASE ADDRESS 1ST CYCLE REVIEW COMMENTS BELOW: |
| | |
| | 1ST REVIEW FMC |
| | PERMIT: 22060778 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE ARE SEVERAL ISSUES WITH THE SUBMITTED DRAWING |
| | FOR THE GREASE DUCT TERMINATION. THE DRAWING DOES NOT |
| | GIVE ANY DETAILS FOR THE STRUCTURE THAT IS BEING |
| | INSTALLED AROUND THE KEF-1, PROVIDE DETAILS AND |
| | DRAWINGS FOR THIS STRUCTURE INCLUDING THE ACCESS DOORS |
| | FOR THE SERVICE AND CLEANING OF THE EQUIPMENT AND |
| | GREASE DUCT. THE DRAWING DOES NOT SHOW THE VEGETATION |
| | IN THE AREA IN QUESTION. PROVIDE A DETAIL SHOWING THE |
| | ACCESS DOORS ABOVE THIS AREA. SHEET H-7 INDICATES THIS |
| | STRUCTURE IS SITTING ON THE CONCRETE SLAB AND THE |
| | MEASUREMENT FROM THE SLAB TO THE BOTTOM OF THE LOUVER |
| | IS A MINIMUM OF 10 FEET. THIS MEASUREMENT SHOULD BE |
| | FROM THE WALKING PAVERS AND NOT FROM THE CONCRETE SLAB |
| | AS WE HAVE NO WAY OF KNOWING HOW HIGH FROM THE SLAB THE |
| | PAVERS ARE RAISED. WE DO KNOW THAT THE LOUVER SHOULD BE |
| | AT LEAST 10 FEET FROM ADJOINING GRADE. FMC 506.3.13.3. |
| | FBC 107.3.5 |
| | |
| | 2) HOW IS THIS STRUCTURE THAT IS SUPPORTING THE EXHAUST |
| | LOUVER SECURED? FBC 107.3.5 |
| | |
| | 3) PROVIDE A DETAIL FOR THE SLEEVE WHERE THE GREASE |
| | DUCT PENETRATES THE ROOF, HOW IS THIS CAPPED? FBC |
| | 107.3.5 |
| | |
| | 4) PROVIDE A DETAIL SHOWING THE CLEARANCE FROM THE |
| | BUILDING TO THE EXHAUST FAN AND THE GREASE EXHAUST |
| | DUCTWORK. FBC 107.3.5 |
| | |
| | 5) SHOW THE DEPTH OF THE STRUCTURE FROM THE BUILDING. |
| | |
| | FMC 503.13.3 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE |
| | NOT LESS THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS |
| | OF THE SAME OR CONTIGUOUS BUILDING, AN ADJACENT |
| | BUILDING, ADJACENT PROPERTY LINE AND AIR INTAKE |
| | OPENINGS INTO A BUILDING WHERE AIR FROM THE EXHAUST |
| | OUTLET DISCHARGES AWAY FROM SUCH LOCATIONS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |