2022-08-29 11:49:531ST REVIEW FMC
 PERMIT: 22060778
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE SEVERAL ISSUES WITH THE SUBMITTED DRAWING
 FOR THE GREASE DUCT TERMINATION. THE DRAWING DOES NOT
 GIVE ANY DETAILS FOR THE STRUCTURE THAT IS BEING
 INSTALLED AROUND THE KEF-1, PROVIDE DETAILS AND
 DRAWINGS FOR THIS STRUCTURE INCLUDING THE ACCESS DOORS
 FOR THE SERVICE AND CLEANING OF THE EQUIPMENT AND
 GREASE DUCT. THE DRAWING DOES NOT SHOW THE VEGETATION
 IN THE AREA IN QUESTION. PROVIDE A DETAIL SHOWING THE
 ACCESS DOORS ABOVE THIS AREA. SHEET H-7 INDICATES THIS
 STRUCTURE IS SITTING ON THE CONCRETE SLAB AND THE
 MEASUREMENT FROM THE SLAB TO THE BOTTOM OF THE LOUVER
 IS A MINIMUM OF 10 FEET. THIS MEASUREMENT SHOULD BE
 FROM THE WALKING PAVERS AND NOT FROM THE CONCRETE SLAB
 AS WE HAVE NO WAY OF KNOWING HOW HIGH FROM THE SLAB THE
 PAVERS ARE RAISED. WE DO KNOW THAT THE LOUVER SHOULD BE
 AT LEAST 10 FEET FROM ADJOINING GRADE. FMC 506.3.13.3.
 FBC 107.3.5
  
 2) HOW IS THIS STRUCTURE THAT IS SUPPORTING THE EXHAUST
 LOUVER SECURED? FBC 107.3.5
  
 3) PROVIDE A DETAIL FOR THE SLEEVE WHERE THE GREASE
 DUCT PENETRATES THE ROOF, HOW IS THIS CAPPED? FBC
 107.3.5
  
 4) PROVIDE A DETAIL SHOWING THE CLEARANCE FROM THE
 BUILDING TO THE EXHAUST FAN AND THE GREASE EXHAUST
 DUCTWORK. FBC 107.3.5
  
 5) SHOW THE DEPTH OF THE STRUCTURE FROM THE BUILDING.
  
 FMC 503.13.3 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE
 NOT LESS THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDING, AN ADJACENT
 BUILDING, ADJACENT PROPERTY LINE AND AIR INTAKE
 OPENINGS INTO A BUILDING WHERE AIR FROM THE EXHAUST
 OUTLET DISCHARGES AWAY FROM SUCH LOCATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  