2022-07-11 10:49:19SHEET H-6 SHOWS THE KEF-1 EXHAUST TERMINATION
 APPROXIMATELY 6 FT. 3.75 INCHES FROM THE PARKING GARAGE
 WALL AND 1 FT 8.75 INCHES FROM THE WALKING AREA OF THE
 GREEN SPACE. THIS DOES NOT MEET FMC 506.3.13.3. THE
 GREEN SPACE IS AN AREA ON THE ROOF THAT THE EMPLOYEES
 CAN SIT AND ENJOY THE OUTDOORS. THIS WOULD BE
 CONSIDERED GRADE LEVEL. PLEASE REVISE THE DRAWING SO
 THAT IT REFLECTS FMC 506.3.13.3
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  