| Plan Review Notes For Permit 22060778 |
| Permit Number |
22060778 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-11 10:49:19 | SHEET H-6 SHOWS THE KEF-1 EXHAUST TERMINATION | | | APPROXIMATELY 6 FT. 3.75 INCHES FROM THE PARKING GARAGE | | | WALL AND 1 FT 8.75 INCHES FROM THE WALKING AREA OF THE | | | GREEN SPACE. THIS DOES NOT MEET FMC 506.3.13.3. THE | | | GREEN SPACE IS AN AREA ON THE ROOF THAT THE EMPLOYEES | | | CAN SIT AND ENJOY THE OUTDOORS. THIS WOULD BE | | | CONSIDERED GRADE LEVEL. PLEASE REVISE THE DRAWING SO | | | THAT IT REFLECTS FMC 506.3.13.3 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|