2022-09-02 07:52:521) PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM FOR THE
 EXISTING HOUSE MECHANICAL UNIT CHANGE OUT. FBC 107.3.5
  
 2) THIS REVIEWER CANNOT SEE HOW THE SUPPLY AND RETURN
 FROM THE FIRST FLOOR IS COMING FROM THE MECHANICAL
 SYSTEM IN THE ATTIC.PLEASE SHOW DETAIL. FBC 107.3.5
  
 3) WITH THE MECHANICAL SYSTEM IN THE ATTIC I DO NOT SEE
 HOW THE RETURN IN THE 2ND FLOOR NEW BEDROOM NORTH WOULD
 BE THE CENTRAL RETURN FOR THE SYSTEM AS THERE IS NO
 DUCTWORK SHOWN IN THE HALL FROM THAT RETURN. THE RETURN
 SHOWN IN THE HALL DOES NOT SHOW IT TIED TO THE
 MECHANICAL SYSTEM IN THE ATTIC. FBC 107.3.5
  
 4) I DO NOT SEE A CHASE ON THE 2ND FLOOR SHOWING THE
 RETURN AND SUPPLY TO THE MECHANICAL SYSTEM IN THE
 ATTIC. PROVIDE A DETAIL SHOWING HOW THIS WILL BE
 COMPLETED. FBC 107.3.5
  