| 2022-07-06 12:07:37 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22060754 |
| | 7/6/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1: SHOW THE SOURCE OF THE HOT WATER FOR THE |
| | NEW BATH FIXTURES- SEC. P2801.1 FBC RES. FOR A NEW |
| | WATER HEATER INSTALLATION PLEASE SHOW THE LOCATION ON |
| | THE PLAN PROVIDE AN EQUIPMENT SCHEDULE- SEC. P2801.4 |
| | FBC RES. THE EQUIPMENT SCHEDULE SHALL INDICATE THE MAKE |
| | AND MODEL, TYPE- TANK OR TANKLESS, GALLON SIZE, |
| | EFFICIENCY RATING, AND ELECTRICAL CIRCUITRY. A) PAN AND |
| | PAN DRAIN DETAILS REQUIRED FOR STORAGE TANK |
| | INSTALLATIONS- SEC. P2801.6 FBC RES. |
| | |
| | 2) SHEET P-1: BECAUSE THIS IS A MULTI-FAMILY DWELLING |
| | AN RPZ BACKFLOW PREVENTER IS REQUIRED FOR THE POTABLE |
| | WATER SERVICE- SEC. D WPB UTILITIES CROSS-CONNECTION |
| | MANUAL. PLEASE PLACE A NOTE ON THE PLANS VERIFYING |
| | THERE IS AN EXISTING RPZ BACKFLOW PREVENTER FOR THE |
| | WATER SERVICE, OR NOTE THAT A NEW RPZ WILL BE INSTALLED |
| | UNDER A SEPARATE PERMIT- SECS. C, D, & E WPB UTILITIES |
| | CROSS-CONNECTION MANUAL & SECS. 105.1 & 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |