| Plan Review Notes For Permit 22060754 |
| Permit Number |
22060754 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-06 07:03:24 | 1ST REVIEW FMC | | | PERMIT: 22060754 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS. FEC 101.5.2.1.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7.1 | | | | | | 3) IT IS UNCLEAR AS TO THE LOCATION OF THE GROUND FLOOR | | | AHU. PLEASE PROVIDE A MECHANICAL DRAWING INDICATING THE | | | LOCATION OF THIS UNIT. FBC 107.2.1 | | | | | | 4) THE APPLICATION IS FOR A NEW ADDITION TO AN EXISTING | | | HOUSE. THE AHU?S PAGE IS LABELED NEW AIR HANDLER FOR | | | OLD HOUSE. THE CONDENSER IS LABELED NEW CONDENSER OLD | | | HOUSE. PROVIDE A COMPLETE SCOPE OF WORK FOR THE | | | MECHANICAL SYSTEMS FOR THIS PROJECT. IS THE AHU?S IN | | | THE EXISTING HOUSE BEING CHANGED OUT? FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|