Plan Review Notes
Plan Review Notes For Permit 22060754
Permit Number 22060754
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-06 07:03:241ST REVIEW FMC
 PERMIT: 22060754
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FEC 101.5.2.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC R403.7.1
  
 3) IT IS UNCLEAR AS TO THE LOCATION OF THE GROUND FLOOR
 AHU. PLEASE PROVIDE A MECHANICAL DRAWING INDICATING THE
 LOCATION OF THIS UNIT. FBC 107.2.1
  
 4) THE APPLICATION IS FOR A NEW ADDITION TO AN EXISTING
 HOUSE. THE AHU?S PAGE IS LABELED NEW AIR HANDLER FOR
 OLD HOUSE. THE CONDENSER IS LABELED NEW CONDENSER OLD
 HOUSE. PROVIDE A COMPLETE SCOPE OF WORK FOR THE
 MECHANICAL SYSTEMS FOR THIS PROJECT. IS THE AHU?S IN
 THE EXISTING HOUSE BEING CHANGED OUT? FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  