| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, ON PLAN SHEET A-5, DESIGN CRITERIA, |
| | THE BUILDING TYPE FOR COMPONENT & CLADDING IS LABELED |
| | AS OPEN. IT APPEARS THAT THIS SHOULD BE ENCLOSED. |
| | PLEASE CLARIFY OR CHANGE TO ENCLOSED. |
| | |
| | 2.) FBC B 107.2.1, THERE ARE NO DETAILS FOR THE TIE-IN |
| | OF NEW TO EXISTING BUILDINGS. PLEASE PROVIDE DETAILS |
| | FOR THE CONNECTION OF NEW TO EXISTING BUILDING AND |
| | INCLUDE THE METHOD OF WATER PROOFING JOINTS OF THE VOID |
| | BETWEEN BUILDING SECTIONS. |
| | |
| | 3.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVALS FOR |
| | FOAM SPRAY INSULATION. |
| | |
| | 4.) FBC R 806.5, PROVIDE DETAILS INCLUDING THE AIR |
| | IMPERMIABILITY OF INSULATION AS PER THIS SECTION OF |
| | CODE AS PLAN SHEET A-6 INDICATES NO VENTS WITH FOAMED |
| | ROOF. |
| | |
| | 5.) FBC R 1003.18, FBC R 1006, & FBC B 107.2.1, ON PLAN |
| | SHEETS: 000 COVER SHEET & A-4 THERE ARE INDICATORS OF A |
| | CHIMNEY. HOWEVER THERE ARE NO INDICATIONS ON OTHER |
| | PAGES OF CHIMNEY. PLEASE CLARIFY AND PROVIDE DETAILS |
| | AND INCLUDE REQUIRED MODIFICATIONS OF WALL FRAMING AND |
| | FLOOR/ROOF TRUSSES FOR REQUIRED CLEARANCE SEPERATION. |
| | |
| | 6.) FBC R 314.3 & FBC R 315.1, PROVIDE, ON PLANS, THE |
| | SMOKE & CARBON MONOXIDE DETECTOR LOCATIONS. |
| | |
| | 7.) FBC EC (R) 103.1.1.2 THE ENERGY CALCULATIONS (FORM |
| | R405) MUST BE COMPLETED AND SIGNED BY OWNER/OWNER'S |
| | REPRESENTATIVE. |
| | |